| 2006-11-28 13:04:05 | **** UNSAT **** |
| | REVISION #7 |
| | |
| | ** PLEASE SEE THE FOLLOWING COMMENTS AS PLANS ARE |
| | COMING BACK WITH SOME REVISIONS; HOWEVER THERE ARE |
| | ITEMS NOW SHOWN AGAIN WHICH WERE COMMENTED ON AND |
| | CORRECTED FROM 2 REVIEWS AGO. |
| | PLEASE GO OVER PLANS CAREFULLY AND PLEASE CALL IF THERE |
| | ARE ANY QUESTIONS OR COMMENTS BASED ON THE FOLLOWING |
| | NOTES TYPED FOR THIS REVIEW. |
| | THIS IS REVISION NUMBER #7, UNLIKE THE PLANS WHICH |
| | INDICATE REVISION #5. |
| | |
| | 1) NOTE: PLEASE KNOW ONE ITEM WHICH HAS BEEN GETTING |
| | REDLINED ON PLANS FROM THE PREVIOUS REVIEWS INCLUDING |
| | THE JOBSITE PLANS IS THE ADDRESS. PLEASE SEE THE |
| | ADDRESS IN OUR SYSTEM AND THE PERMITTED ADDRESS IS |
| | "6429", WHERE THE PLANS INDICATE "6425". THIS REVIEWER |
| | HAS BEEN CHANGING THIS BY HAND ON PLANS TO HELP IN |
| | GETTING THE REVISIONS DONE, HOWEVER AS PLANS ARE COMING |
| | BACK FOR OTHER COMMENTS PLEASE ADJUST THIS AT THIS |
| | TIME. |
| | PLEASE DO NOT KEEP SUBMITTING PLANS WITH THE OLD |
| | ADDRESS. |
| | FAC 61G1-16.004 |
| | |
| | 2) NOTE: PLEASE SEE THE POOL PANEL IS NOW MISSING FROM |
| | THE PLANS??? PLEASE SEE THE RISER STILL SHOWS THIS |
| | PANEL AND THERE IS A PANEL SCHEDULE SUBMITTED FOR THIS, |
| | YET PLANS WHICH PREVIOUSLY SHOWED THIS PANEL NO LONGER |
| | DOES? |
| | PLEASE SHOW. |
| | 110.26, 240.24 ETC |
| | FBC ADMIN SECTION 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE PLANS NOW REPLACE THE DESIGNATION |
| | FOR WHAT USED TO BE THE SUB PANEL "B" TO NOW |
| | DESIGNATION FOR A SUB PANEL "E". PLEASE SEE THE RISER |
| | AND THE PANEL SCHEDULES DO NOT CORRELATE WITH THIS. |
| | IS THERE ANOTHER PANEL?? |
| | FBC 106.1.2 |
| | |
| | 4) NOTE: PLEASE SEE THE SUB PANEL B HAS NOW CHANGED THE |
| | FEEDERS ON THE RISER; HOWEVER THE PANEL SCHEDULE "A" |
| | STILL SHOWS #4'S?? |
| | PLEASE CORRELATE THE SIZE OF THE FEEDERS AND VERIFY THE |
| | PANEL SIZE AS IT IS NOT KNOW THAT A 70A PANEL IS MADE? |
| | PLEASE KNOW IF THIS IS A 100A MLO, IT IS OK SHOWING A |
| | 70A BREAKER IN PANEL ?A? FEED TO THIS PANEL. |
| | PLEASE CORRELATE AND SIZE CORRECTLY. |
| | 408.4, 310.16, ETC |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE SEE AHU WHICH HAS NOW CHANGED TO 8KW, |
| | YET STILL SHOWS 10KW? PLEASE CORRELATE AND ADJUST THE |
| | OVER CURRENT PROTECTION, CONDUCTOR SIZES ETC AS NEED. |
| | 310.16, 424.3B, 240.4 ETC |
| | |
| | 6) NOTE: PLEASE SEE ONE OF THE WATER HEATERS WHICH WERE |
| | SHOWN AS GAS ON THE PREVIOUS PLANS, HAVE NOW CHANGED TO |
| | ELECTRIC SHOWING A 4.5KW LOAD YET STILL SHOW FEEDING |
| | THIS WATER HEATER WITH A SINGLE POLE 20A CIRCUIT? |
| | PLEASE ADJUST AND CORRELATE. IF SOLAR THEN PLEASE |
| | SUBMIT THE SPEC/INFORMATION FOR THIS AS THIS IS THE |
| | FIRST PLAN WHICH INDICATES ANY SOLAR WATER HEATER. |
| | PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS FOR THIS |
| | EQUIPMENT. 110.3, 90.7 |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | 7) NOTE: PLEASE SEE NOTES WHICH WERE ON PREVIOUS PLANS |
| | WHICH MENTIONED THE SMOKE DETECTORS BEING PART OF THE |
| | LOW VOLTAGE SECURITY, YET THESE NOTES HAVE BEEN REMOVED |
| | FROM BOTH SHEETS? PLEASE CLARIFY. IF THIS IS INDEED THE |
| | CASE PLEASE REPLACE NOTES, IF NOT PLEASE INDICATE AS |
| | "SA" FOR SMOKE ALARMS WHICH IS PART OF A 120V SYSTEM |
| | WHICH CONTAINS AN DETECTION AND ALARM IN THE SAME UNIT |
| | DEVICE. |
| | PLEASE SEE NFPA-72 DEFINITIONS FOR THIS. |
| | |
| | **** AS MENTIONED ON ALL PREVIOUS REVIEWS, IF THERE ARE |
| | ANY QUESTIONS, COMMENTS OR IF ANY OF THE COMMENTS ARE |
| | CONFUSING OR NOT UNDERSTOOD IN ANY WAY, PLEASE CALL. |
| | TO DATE THIS OFFICE HAS NOT RECEIVED ANY CALLS FROM THE |
| | ARCHITECT OF RECORD OVER THE LAST 6 OR SO REVIEWS WHICH |
| | HAVE BEEN DONE. |
| | |
| | |