| 2006-10-13 18:48:57 | ****UNSAT **** |
| | |
| | 1) NOTE: PLEASE CORRELATE RISER , PLANS AND PANEL |
| | SCHEDULE SUBMITTED. PLEASE SEE PANEL "E" WAS NOT SHOWN, |
| | HOWEVER TWO 200A PANEL "A"'S ARE?? |
| | FBC106.1.2 PLEASE KNOW AT THIS TIME SOME REVIEW OF |
| | ITEMS CAN NOT BE VERIFIED FOR CODE COMPLIANCE. PLEASE |
| | SEE THAT IS IS BEING "ASSUMED" THAT THE SECOND PANEL |
| | "A" IS ACUTALLY PANEL "E", YET THIS PANEL LOAD DOES NOT |
| | CORRELATE WITH LOAD ON PANEL "B" WHICH IS NOTED AS |
| | FEEDING "E". PLEASE ALSO SEE THIS PANEL IS BEING SHOWN |
| | AS 200A. |
| | |
| | 2) NOTE: PLEASE CORRELATE PANEL SCHEDULES WITH PLANS |
| | AND CIRCUITING. PLEASE SEE THAT THERE ARE NUMEROUS |
| | ITEMS WHICH DO NOT MATCH. PLEASE SEE MANY OF THESE |
| | ITEMS ARE REDLINED ON PLANS HOWEVER A FEW ARE NOTED |
| | BELOW TO SEE WHAT IS BEING MENTIONED. |
| | PLEASE SEE JACUZZI/WHIRLPOOL TUB, SHOWS 220V AND ON TWO |
| | PHASES AS 220V, YET SCHEDULE SHOWS 1-POLE? |
| | PLEASE SEE B-24 WHICH IS SHOWN AS ICE MAKER, YET PLANS |
| | ALSO SHOW THIS FEEDING FAN IN OFFICE. |
| | PLEASE SEE B-29 WHICH IS SHOWN FEEDING FAN ALSO FEEDS |
| | THE SAME JACUZZI CIRCUIT ABOVE. |
| | PLEASE SEE A-15 WHICH FEEDS BATH(S) RECEPTS ALONG WITH |
| | NUMEROUS RECEPTS IN LIVING ROOM AND GARAGE. (PLEASE SEE |
| | 210.11C3,AS THE REQUIRED DEDICATED BATH(S) CIRCUIT(S) |
| | ARE NOT PERMITTED TO FEED ANY OTHER AREAS. |
| | PLEASE SEE SMOKE ALARMS BEING SHOWN ON MORE THAN ONE |
| | CIRCUIT IS IS NOT POSSIBLE AS THESE ARE REQUIRED TO BE |
| | WIRED "INLINE". IFON MORE THAN ONE CIRCUIT THIS WOULD |
| | NOT WORK OR CREATE 220V TO A 120 UNIT. |
| | PLEASE SEE B-30, SHOWS WINE UNIT ON PLANS, YET B-30 IS |
| | PART OF THE CIRCUIT WHICH IS SHOWN FEEDING PANEL "E" |
| | PLEASE SEE WH AND CENTRAL VAC BEING SHOWN ON THE SAME |
| | CIRCUIT. A-18. |
| | ETC. |
| | |
| | 3) NOTE: PLEASE SEE 20A BREAKER(S) ON CONDUCTORS ONLY |
| | RATED FOR 15A'S PER 310.16. PLEASE SEE 240.4. |
| | |
| | |
| | ** PLEASE KNOW, AS THERE ARE MANY ITEMS WHICH NEED |
| | CORRELATING , PLEASE BE SURE TO CALL IF THERE ARE NAY |
| | QUESTIONS. |
| | |
| | |