| 2005-12-14 00:00:00 | **** UNSAT 3RD REVIEW **** |
| | |
| | ** PLEASE SEE NOTES FROM PREVIOUS REVIEW |
| | AND NEW NOTES DUE TO CHANGES IN PLANS. |
| | |
| | |
| | 1)NOTE: PLEASE SEE NOTE #1 FROM PREVIOUS |
| | REVIEW WHICH REQUESTED TO SHOW THE |
| | POWER/OUTLET LOCAION ON PLANS FOR |
| | JACUZZI TUB. THIS WAS DONE , HOWEVER NOW |
| | THIS ISNOW SHOWING CIRCUITING ON PLANS |
| | FOR A 2-POLE UNIT(CIRCUITS 35 AND 37), |
| | PLEASE SEE PANEL SCHEDULE SHOWS THIS A A |
| | 1-POLE 30A. |
| | PLEASE CORRELATE |
| | |
| | 2)NOTE: PLEASE SEE NOTE #21 FROM |
| | PREVIOUS REVIEWS WHICH REQUESTED THE |
| | NEED TO CORRELATE THE RISER DIAGRAM, |
| | PANEL SCHEDULES ETC. |
| | |
| | A) PLEASE SEE RISER DIAGRAM STILL SHOWS |
| | TWO 200A DISCONNECTS WITH 200A FUSES, |
| | ALTHOUGH PANEL SCHEDULES ARE SUBMITTED |
| | INDICATING THESE AS 200A PANELS |
| | ("C"&"D") WITH NO INDICATION OF HAVING |
| | MCB'S??? |
| | |
| | B)PLEASE ALSO SEE RISER INDICATES PANELS |
| | "A" AND "B" AS MAIN BREAKER PANELS, AND |
| | THESE PANEL SCHEDULES SHOWS MLO (MAIN |
| | LUG ONLY)?? |
| | |
| | C)PLEASE NOW ALSO SEE PANEL SCHEDULES C |
| | AND D, INDICATE #2 FOR THE 200A FEED TO |
| | PANELS A AND B. PLEASE SEE 240.4, AND |
| | 310.15B6/16 FOR THE MIN 2/0. |
| | |
| | 3)NOTE: PLEASE SEE NOTE #4 FROM PREVIOUS |
| | REVIEW WHICH STATED THE SD'S WERE ON |
| | MORE THAN ONE CIRCUIT A-19 AND B-13. |
| | PLEASE SEE CIRCUITING WAS REVISED ON 2ND |
| | FLR TO CIRCUIT A-24, HOWEVER FIRST FLR |
| | IS SHOWN AS A-13?? |
| | ** PLEASE KNOW, THE SD'S ARE REQUIRED TO |
| | BE WIRED "INLINE" AND CAN NOT BE ON TWO |
| | SEPARATE CIRCUITS. THIS WOULD BE SENDING |
| | 220V TO THE 120V SD"S. |
| | PLEASE ALSO SEE PLANS NOW HAVE A NOTE |
| | ADDED FOR SD'S WHICH REFERENCE THE OLD |
| | NFPA-72 8-1 |
| | PLEASE SEE AS OF JAN 1ST, 2005, NFPA-72 |
| | HAS CHANGED TO THE 2002 EDITION AND |
| | CODES FOR SD'S REFERENCE SHOULD BE |
| | 11.5.1.1. |
| | |
| | 4)NOTE: PLEASE SEE PREVIOUS NOTE #5 |
| | WHICH MENTIONED CIRCUITING FOR MASTER |
| | BATH WAS IN ERROR. PLEASE SEE CIRCUITING |
| | FOR THIS MASTER BATH HAS NOW BEEN |
| | REVISED, HOWEVER PLEASE SEE PANEL |
| | SCHEDULE NOW MENTIONS THIS AS ARC FAULT |
| | AND ON THE SAME CIRCUIT AS THE MASTER |
| | BEDROOM. |
| | PLEASE SEE 210.52D,210.11C3 |
| | |
| | 5)NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) ATTACHED WITH RESPECT TO |
| | THE DESIGN PROFESSIONAL AND REPEAT |
| | COMMENTS FOR CODE COMPLIANCE. IF PLANS |
| | COME BACK FOR REVIEW WITH ANY OF THE |
| | SAME CODE COMPLIANCE COMMENTS NOT |
| | ADDRESSED THIS OFFICE WILL HAVE NO |
| | CHOICE BUT TO ISSUE A 4X THE FEE FOR |
| | SAID REVIEW COMMENTS. |
| | THIS AMOUNT WOULD BE $12,600.00. |
| | ** TO THIS DATE NO ONE HAS CALLED TO GO |
| | OVER ANY COMMENTS IF THERE WERE ANY |
| | QUESTIONS, PLEASE KNOW IT IS STRONGLY |
| | SUGGESTED THAT A MEETING BE HELD TO GO |
| | OVER COMMENTS AND PLANS BEFORE |
| | RE-SUBMITTING PLANS FOR REVIEW AND ANY |
| | POSSIBLITY OF THE ABOVE BEING |
| | IMPLEMENTED. |
| | |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | MYSELF TO MEET AND/OR GO OVER THE ABOVE |
| | REFERENCED COMMENTS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |