| 2005-11-09 00:00:00 | ***** UNSAT **** |
| | |
| | PLEASE SEE SOME COMMENTS FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED ALONG |
| | WITH SOME COMMENTS DUE TO CHANGES ETC. |
| | |
| | 1)NOTE: PLEASE INDICATE THE POWER OUTLET |
| | LOCATION FOR JACUZZI TUB AT TUB |
| | LOCATION. |
| | |
| | 2)NOTE: PLEASE CORRELATE RISER AND PANEL |
| | SCHEDULES. |
| | PLEASE KNOW THIS IS PART OF NOTES #5AND |
| | #7 FROM PREVIOUS REVIEW. |
| | PLEASE SEE RISER INDICATES 200A FUSED |
| | DISCONNECTS, HOWEVER PLANS AND PANEL |
| | SCHEDULES SEEM TO INDICATE THESE AS MCB |
| | PANELS? PLEASE ADJUST. |
| | PLEASE ALSO SEE WHAT APPEARS TO BE TWO |
| | PANELS OUTSIDE AND TWO INSIDE ARE ALL |
| | LABELED AS "A"S AND "B". PLEASE SEE |
| | MAYBE THESE SHOULD BE"A" AND "A1" AND |
| | "B" AND "B2" OR SOME OTHER METHOD OF |
| | LABELING EACH ONE SPECIFIC. |
| | PLEASE SEE PREVIOUS NOTES MENTIONED THE |
| | LOAD ABOVE THE 150A PANELS SHOWN, |
| | HOWEVER PANELS FOR "B" AND "B" ARE STILL |
| | SHOWN AS 150A WITH LOADS EXCEEDING THIS |
| | RATING. |
| | PLEASE SEE RISER HOWEVER SHOWS 200A'S AS |
| | ADJUSTED FROM NOTES. |
| | PLEASE CORRELATE ALL. |
| | 215.5,240.4,310.16 ETC. |
| | |
| | 3)NOTE: PLEASE SEE REDLINED PLANS FOR |
| | MISSING RECEPT FOR 2' OF WALL. LIV RM |
| | |
| | 4)NOTE: PLEASE SEE SD'S ON FIRST FLR ARE |
| | CIRCUITED TO A-13, HOWEVER 2ND FLR MOST |
| | DO NOT INDICATE THE CIRCUIT, ALTHOUGH |
| | ONE AT MASTER BEDRM SEEMS TO SHOW |
| | "B-13", |
| | |
| | 5)NOTE: PLEASE SEE MASTER BATH CIRCUIT |
| | AS A-19, YET PANEL SCHEDULE SHOWS AS |
| | SPARE. |
| | PLEASE ALSO SEE ICE MAKER SHOWN AS WINE |
| | COOLER, BATH CIRCUIT B-21 , LABEL AS |
| | EXTERIOR RECEPTS, ALTHOUGH THERE ARE EXT |
| | RECEPTS ON THE SAME B-21 CIRCUIT. |
| | PLEASE ADJUST AND CORRELATE AS MUCH AS |
| | POSSIBLE AT THIS TIME. |
| | IT WILL BE INEVITABLE THAT OTHER |
| | REVISIONS AND CHANGES DURING |
| | CONSTRUCTION WILL HAPPEN. |
| | |
| | ** PLEASE SEE ZONING COMMENTS, IT IS |
| | NOTED BY ELECTRICAL REVIEW, THAT A |
| | REVISED "SITE-PLAN" AND SURVEY WAS |
| | SUBMITTED. |
| | THIS DID NOT AFFECT ELECTRICAL PLANS AT |
| | THIS TIME. |
| | |
| | |