| Date |
Text |
| 2005-08-16 00:00:00 | ************* UNSAT ****************** |
| | |
| | 1)NOTE: PLEASE SEE ZONING COMMENTS WHICH |
| | WILL HAVE A DIRECT AFFECT ON ELECTRICAL |
| | AND OTHER PLANS FOR HOUSE. |
| | PLEASE SEE BLDG REVIEW COMMENTS, SURVEY |
| | MUST CONTAIN AN ORIGINAL SIGNATURE FROM |
| | THE SURVEYOR OF RECORD. FS 472.025, FAC |
| | 61G17-7.002 |
| | |
| | 2)NOTE: PLEASE SEE POOL/ POOL WIRING |
| | SHALL BE UNDER A SEPARATE PERMIT. |
| | |
| | 3)NOTE: PLEASE CORRELATE ALL CIRCUITING |
| | SHOWN ON PLANS WITH THE PANEL SCHEDULES |
| | SUBMITTED. PLEASE SEE THERE ARE NUMEROUS |
| | CIRCUITS ON PLANS ETC WHICH DO NOT |
| | MATCH. |
| | PLEASE SEE COOK-TOP, TWO SETS OF |
| | DISHWASHER/ DISP,(NOT ON PLANS), SEE |
| | FLOOD LTS, WHIRLPOOL ETC. |
| | MMANY OF THESE HAVE BEEN REDLINED ON |
| | PLANS. |
| | |
| | 4)NOTE: PLEASE SEE WHIRLPOOL WHICH IS |
| | SHOWN AS GEN LTS AND BEDRM CIRCUIT, IS |
| | REQUIRED TO HAVE GFI PROTECTION. PLEASE |
| | NOTE ON PANEL SCHEDULE, PLEASE SHOW |
| | LOCATION OF POWER OUTLET LOCATED AT WP |
| | TUB. PLEASE INDICATE REQUIRED ACCESS. |
| | |
| | 5)NOTE: PLEASE SHOW LOCATIONS OF ALL |
| | SERVICE EQUIPMENT ON PLANS. PLEASE SEE |
| | METER ONLY SEEMS TO SHOW A DISC LOCATED |
| | NEXT TO IT. |
| | PLEASE SEE PANEL SCHEDULES ARE INDICATED |
| | AS "MAIN DISC'S" AND RISER SHOWS THESE |
| | AS MCB PANELS? PLEASE VERIFY IF THESE |
| | ARE "FEED- THRU" PANELS OR IS THERE OCP |
| | LOCATED IN EACH OF THESE PANELS FEEDING |
| | SUB-PANELS? |
| | 215.5 |
| | |
| | 6)NOTE: PLEASE SEE NOTE ON PLANS |
| | MENTIONS, FPL TO USE 1/0 ALUM? PLEASE |
| | VERIFY THIS WITH A FPL SERVICE PLANNER |
| | AS SERVICE AND LOADS PROPOSED WOULD |
| | EXCEED FPL STANDARDS FOR 1/0'S AND A |
| | 400A SERVICE. |
| | 215.5 |
| | |
| | 7)NOTE: PLEASE SEE MAIN/PANEL "B" LOAD |
| | EXCEEDS, "FUTURE" PLANNING FOR ADDED |
| | LOADS. PLEASE SEE PANEL "B" WILL BE |
| | REQUIRED TO BE UPGRADED TO A MIN OF |
| | 200A'S. PLEASE ADJUST. |
| | 90.4,90.8 |
| | |
| | 8)NOTE: PLEASE SEE AN "EUIPMENT |
| | GROUNDING" CONDUCTOR IS ONLY INSTALLED |
| | AFTER THE FIRST MEANS OF DISCONNECT. |
| | PLEASE SEE AN EQUIPMENT GRND IS SHOWN |
| | FROM METER TO MAIN. |
| | 250.6, 250.24 PLEASE REMOVE. |
| | |
| | 9)NOTE: PLEASE SEE MIN GROUNDING |
| | ELECTRODE CONDUCTOR IS TO BE A 1/0 BASED |
| | ON 250.66, 310.15B6 |
| | PLEASE ADJUST, #2 SHOWN. |
| | |
| | 10)NOTE: PLEASE SEE 210.52C1 AND |
| | REDLINED PLANS FOR GFI RECEPTS REQUIRED |
| | ALONG KITCHEN COUNTERSPACE. |
| | |
| | 11)NOTE: PLEASE SEE 210.8, ALL RECEPTS, |
| | LOCATED OUTSIDE, WITIN 6' OF ANY SINK, |
| | ETC SHALL BE GFI/GFI PROTECTED. PLEASE |
| | SEE , BAR AREAS, LAUNDRY RMS ETC. |
| | MANY OF THESE REDLINED ON PLANS. |
| | |
| | 12)NOTE: PLEASE SEE ALL RECEPT SHOWN |
| | WITHIN 10' OF POOL ARE NOT PERMITTED AND |
| | MUST BE REMOVED. PLEASE SEE 680.22 |
| | AMIN OF (1) GFI RECEPT IS REQUIRED |
| | WITH 20' OF A POOL BUT MUST BE ATLEAST |
| | 10' FROM WATERS EDGE. PLEASE SEE THERE |
| | ARE RECEPTS SHOWN WITHIN THE 10' WHICH |
| | PROMOTES A "LIFE SAFETY" SITUATION. |
| | PLEASE ALSO SEE 680.22B4, FOR LIGHT |
| | FIXTURES NOT PERMITTED WITHIN 5'OF |
| | POOL'S WATER EDGE. PLEASE SEE ANY LTS |
| | WITHIN 5-10' , MUST BE ATLEAST 5' ABOVE |
| | MAX WATER LINE AND MUST ALSO BE GFI |
| | PROTECTED. PLEASE SEE SOME FIXTURES MAY |
| | NOT BE INSTALLED AT ALL , AS THEY ARE |
| | LESS THAN 5' FROMWATER'S EDGE. |
| | THIS IS A "LIFE SAFETY" SITUATION. |
| | |
| | 13)NOTE: PLEASE SEE 210.52 FOR MISSING |
| | RECEPTS PER 2', 6', AND 12' RULE. |
| | PLEASE SEE MANY OF THESE AREAS ARE |
| | REDLINED ON PLANS AT LOCATIONS BUT NOT |
| | ALL. |
| | PLEASE SEE ATRIUM,OFFICE, FAMILY RM, |
| | LIVING RM ETC. |
| | |
| | 14)NOTE: PLEASE SEE RECEPT SHOWN FOR |
| | OUTSIDE WINE CU, TO BE GFI 210.8 |
| | |
| | 15)NOTE: PLEASE SEE 110.26 FOR MIN |
| | CLEARNECE REQUIRED FOR A/C CU |
| | DISCONNECTS.440.11 |
| | |
| | 16)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4, |
| | NFPA-72 8-1.4.1.6.2 |
| | PLEASE NOTE INSTALLATION PER NFPA-72 |
| | 8-1.4.2 ON PLANS. |
| | PLEASE SEE MANY OF THE SMOKE DETECTORS |
| | ARE REDLINED ON PLANS. PLEASE SEE OFFICE |
| | WILL BE REQUIRED TO HAVE A SD. |
| | |
| | 17)NOTE: PLEASE SEE A "NOTE" ON PLANS |
| | E-1, MENTIONS ARC FAULT PROTECTION FOR |
| | RECEPTS ONLY. |
| | PLEASE SEE 2002 NEC 210.12,WHICH |
| | REQUIRES ARC FAULT PROTECTION FOR ALL |
| | "OUTLETS". PLEASE SEE E-2 SEEMS TO NOTE |
| | THIS. |
| | |
| | 18)NOTE: PLEASE SEE PLANS "GEN NOTES" |
| | #1, REFERENCE "PALM BEACH COUNTY", |
| | PLEASE SEE, SINCE THIS PROJECT IS |
| | LOCATED IN THE CITY LIMITS, PLANS WOULD |
| | BE REQUIRED TO REFERENCE CITY OF WEST |
| | PALM BEACH. |
| | |
| | 19)NOTE: PLEASE PROVIDE ALL ROOM AND |
| | AREA DESIGNATION(S) ON ELECTRICAL PLANS. |
| | 215.5 |
| | |
| | 20)NOTE: PLEASE SHOW ALL "CONTINUOUS |
| | LOADS" (3 OR MORE HRS)ARE SHOWN AT 125% |
| | ON LOAD CALCULATIONS. |
| | 215.3,230.42 ETC. |
| | |
| | 21)NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | ** PLEASE SEE THERE ARE OVER 110 |
| | RECESSED LT FIXTURES SHOWN. |
| | PLEAS ADJUST LOAD CALCULATIONS. |
| | |
| | 22)NOTE: PLEASE SEE "POOL EQUIPMENT" MAY |
| | NOT BE LOCATED AT LOCATION SHOWN AS |
| | BEING "UNDER" WOOD DECK WITHIN THE POOL |
| | AREA OF 5'. |
| | 680.22 ETC. PLEASE ALSO SEE POSSIBLE |
| | COMMENTS FORM OTHER TRADES. |
| | |
| | 23)NOTE: PLEASE SEE NUMEROUS BATH |
| | RECEPTS CIRCUITS WHICH ARE SHOWN AS #14, |
| | 15A CIRCUITS. PLEASE SEE 210.52,210.11C3 |
| | WHICH REQUIRES DEDICATED BATH(S) |
| | CIRCUIT(S). PLEASE SEE THESE ARE |
| | REQUIRED TO BE 20A AND #12, PLEASE |
| | ADJUST CIRCUITING AND PANEL SCHEDULES. |
| | |
| | 24)NOTE: PLEASE VERIFY OCP SHOWN FOR |
| | AHU#3, THIS IS SHOWN AS A 7.5KW UNIT, |
| | HOWEVER LOAD CALCULATIONS AND OCP SHOW |
| | THIS AS A 10KW UNIT. PLEASE CORRELATE |
| | AND ADJUST. |
| | |
| | 25)NOTE: PLEASE VERIFY GARAGE DOOR |
| | OPENERS AND LOAD (HP RATING) FOR EACH. |
| | PLEASE SEE 430.53 AND POSSIBLE A MIN OF |
| | TWO GDO CIRCUITS. |
| | |
| | 26)NOTE: PLEASE SEE PLANS AND VERIFY ALL |
| | PHONE AND CATV LOCATIONS WHICH ARE GOING |
| | TO BE INCLUDED UNDER THIS PERMIT. |
| | (MASTER BEDRM PHONE?) |
| | THIS IS ONLY A NOTE. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE BE SURE ONE SET OF ALL OLD/VOIDED |
| | SHEETS REMOVED ARE SUBMITTED BACK FOR |
| | REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |