| Date |
Text |
| 2007-06-27 20:04:42 | *** UNSAT*** |
| | |
| | 1) NOTE: PLEASE SEE PERMITTED ISSUED PLANS WERE |
| | REDLINED AND NOTED THAT THE RISER CONDUIT SHOWN AS 2 |
| | 1/2 INCHES WAS NOT LARGE ENOUGH BASED ON THE NEC. |
| | PLEASE SEE CHAPTER 9, TABLE 4 AND 5 FOR FIGURING |
| | CONDUIT FILL OR SEE TABLE C8 FOR DIRECT CONDUIT FILL. |
| | IN EITHER CASE THE MINIMUM CONDUIT SIZE NEEDS TO BE |
| | 3INCH RMC. |
| | |
| | 2) NOTE: PLEASE SEE PANEL SCHEDULE WHICH NOW INDICATE |
| | THE REMOVAL OF THE RANGE AND WATER HEATER AS ELECTRIC |
| | AND ONLY INDICATE SINGLE POLE 20AMP CIRCUITS FOR |
| | CONTROL HOWEVER PLEASE SEE THE SPARE SPACES STILL |
| | INDICATE THE CONDUCTOR SIZES AS #8 AND #12 AS INSTALLED |
| | FOR *B* PHASE. |
| | PLEASE ADJUST AS PLANS ARE NEEDED TO BE 100% FOR |
| | FINAL. |
| | |
| | 3) NOTE: PLEASE SEE THE SHEETS E-3 AND E-4 AS THE TITLE |
| | BLOCKS INDICATE A REVISION #4 HOWEVER NOT REVISION #4 |
| | COULD BE LOCATED ON EITHER OF THESE SHEETS? |
| | PLEASE ONLY SUBMIT SHEETS BEING REVISED OR PLEAS |
| | INDICATE THE REVISION TAKING PLACE. |
| | FBC 106.1.2, 106.1 |
| | |
| | 4) NOTE: PLEASE VERIFY THE LOCATION OF THE CONTROLS FOR |
| | THE NEW GAS WATER HEATERS AS THEY ARE NOW SHOWN OUTSIDE |
| | AND THE LOCATION OF THE RECEPTACLES ARE BEING SHOWN AT |
| | THE OLD/PREVIOUS WATER HEATER LOCATION. |
| | PLEASE CLARIFY THIS: PLEASE KNOW IF THESE RECEPTACLES |
| | ARE FOR THESE UNITS OUTSIDE, PLEASE INDICATE AT THAT |
| | LOCATION ALONG WITH GFI INDICATIONS. |
| | FBC 106.1.2 |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| 2007-06-27 19:28:20 | PLANS REMOVED FROM INCOMING, WILL BE RETURNED TO |
| | INCOMING WHEN ELECTRICAL REVIEW IS DONE. |