| 2007-07-30 09:56:10 | PLUMBING PLAN REVIE DENIED | | | | | | | | | PREVIOUS COMMENT BY KEN STEVENS NOT ADDRESSED DATED | | | 01-02-07 | | | WATER RISER DIAGRAM PAGE P-2 | | | | | | WATER HAMMER ARRESTORS ARE REQUIRED AT THE AUTOMATIC | | | CLOTHES WASHERS. PLEASE SHOW ON DRAWING. | | | ****** RESPONSE NOTED, BUT THE ARRESTORS ARE NOT SHOWN | | | ON BOTH THE HOT AND COLD WATER SUPPLIES. ( ONLY THE | | | COLD) . | | | PLEASE SHOW ON BOTH SUPPLY LINES. SECTION 604.9 | | | | | | REVIEW BY PAUL SCHMITZ 561-805-6692 |
|