2007-07-30 09:56:10PLUMBING PLAN REVIE DENIED
  
  
 PREVIOUS COMMENT BY KEN STEVENS NOT ADDRESSED DATED
 01-02-07
 WATER RISER DIAGRAM PAGE P-2
  
 WATER HAMMER ARRESTORS ARE REQUIRED AT THE AUTOMATIC
 CLOTHES WASHERS. PLEASE SHOW ON DRAWING.
 ****** RESPONSE NOTED, BUT THE ARRESTORS ARE NOT SHOWN
 ON BOTH THE HOT AND COLD WATER SUPPLIES. ( ONLY THE
 COLD) .
 PLEASE SHOW ON BOTH SUPPLY LINES. SECTION 604.9
  
 REVIEW BY PAUL SCHMITZ 561-805-6692