Plan Review Notes
Plan Review Notes For Permit 05080077
Permit Number 05080077
Review Stop P
Sequence Number 6
Notes
Date Text
2007-01-02 16:41:47DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW BY JOHN LEECH:
  
 4. ENGINEER IS REQUIRED TO SIGN PLANS, NOT INITIAL.
 ****RESPONSE NOTED, BUT P-3 STILL NOT SIGNED. FAC
 61G15-23.002(2) & FS 471.2055.
  
 5. WATER RISER DIAGRAM PAGE P-2. WATER HAMMER ARRESTORS
 ARE REQUIRED AT THE AUTOMATIC CLOTHES WASHERS. PLEASE
 SHOW ON DRAWING.
 ****RESPONSE NOTED, BUT THE ARRESTORS ARE NOT SHOWN ON
 BOTH THE HOT AND COLD WATER SUPPLIES. (ONLY THE COLD).
 PLEASE SHOW ON BOTH SUPPLY LINES. SECTION 604.9.
  