Plan Review Notes
Plan Review Notes For Permit 05080077
Permit Number 05080077
Review Stop E
Sequence Number 6
Notes
Date Text
2006-12-24 18:33:08*** UNSAT 6TH REVIEW ***
  
  
 *** PLEASE SEE THAT SOME COMMENTS FROM PREVIOUS REVIEWS
 HAVE STILL NOT BEEN ADDRESSED.
 PLEASE SEE COMMENTS BELOW.
 IT IS GOING TO BE THE ATTEMPT OF THIS REVIEW TO TRY AND
 INDICATE EVERY ITEM AS THE RESPONSE LETTER SEEMS TO
 LEND TO MISUNDERSTANDING OF THE COMMENTS OR THE CODE
 SECTIONS GIVEN.
  
 ** PLEASE KNOW THAT TO DATE OF THIS REVIEW NO CONTACT
 HAS BEEN MADE BY THE DESIGNER OR DESIGN TEAM TO GO OVER
 NOTES FOR QUESTIONS OR COMMENTS.
 AT THE END OF EACH PREVIOUS REVIEW THIS REVIEWER HAS
 PLACED THE DIRECT PHONE NUMBER AND E-MAIL ADDRESS FOR
 THIS PURPOSE.
  
 1) NOTE: PLEASE KNOW A 4X TIME FEE FOR THE PLAN REVIEW
 PORTION OF THE PERMIT FEE HAS NOW BEEN ASSESSED TO THE
 DESIGNER OF RECORD DUE TO COMMENTS BEING REPEAT
 COMMENTS FOR CODE COMPLIANCE.A NOTICE TO FLORIDA
 STATUTES 553.80(2)(B) WAS GIVEN ON PREVIOUS REVIEW.
 PLEASE KNOW THAT THE FEE OF $1,359.60 IS DUE BEFORE
 PLANS MAY BE RESUBMITTED AND IS THE RESPONSIBILITY OF
 THE DESIGNER OF RECORD FOR ELECTRICAL. THIS IS NOT
 ASSESSED TO THE CONTRACTOR OR OWNER OF RECORD. PLEASE
 ALSO KNOW PLANS ARE BEING RETAINED BY THIS OFFICE ONCE
 AGAIN AND NOW MAY BE TURNED INTO THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS FOR REVIEW.
  
 2) NOTE: PLEASE CORRELATE ALL LOADS ON PANEL SCHEDULES
 AND LOAD CALCULATIONS SUBMITTED. PLEASE SEE THIS
 COMMENT HAS BEEN MADE ON EACH OF THE PREVIOUS REVIEWS.
  
 A) PLEASE SEE THE PANEL SCHEDULE AT THE TOP MENTIONS
 "LOAD IN (AMPS)" HOWEVER THIS SEEMS TO BE IMPOSSIBLE AS
 SHOWN. SOME SHOWN IN AMPS, AND OTHER SHOWN IN VA.
  
 B) PLEASE SEE FOR INSTANCE THE LOAD FOR THE RANGE IS
 SHOWN AT 40A?S, HOWEVER THIS DOES NOT CORRELATE WITH
 THE VA IN LOAD CALCULATIONS.
  
 C) PLEASE SEE SEVERAL OTHER CIRCUITS WHICH LOADS ARE
 SHOWN IN AMPS WHICH IS OK, HOWEVER THE AMPERAGE AS
 SHOWN NEEDS TO CORRELATE WITH THE VA SHOWN IN THE LOAD
 CALCULATIONS TO THE LET OF THE PANEL SCHEDULE.
  
 D) PLEASE THEN SEE SOME LOADS ON PANEL SCHEDULE ARE
 BEING SHOWN IN WHAT APPEARS TO BE THE VA FOR EACH
 CIRCUIT. (EXAMPLE, PLEASE SEE SMALL APPLIANCE CIRCUITS
 SHOWN AT 1.5? ARE THESE AMPS AS NOTED ON PANEL SCHEDULE
 OR THE ACTUAL VA, WHICH IS 1500VA? PLEASE ALSO SEE BATH
 ROOM CIRCUIT ETC.
  
 E) PLEASE SEE TOTAL CONNECTED LOAD ON PANEL SCHEDULE
 SHOWS 20.8, YET LOAD CALCULATIONS INDICATE 19,768.
  
 F) PLEASE SEE WASHER IS STILL BEING SHOWN ON A SINGLE
 POLE 30A CIRCUIT WITH #10 AWG, YET PLEASE SEE UPPER
 PLANS WHICH MENTION A 10AMP CIRCUIT FOR WASHER? (THE
 MINIMUM REQUIRED AND LOADS NEED TO CORRELATE FOR THIS.
 PLEASE ALSO SEE 210.21(B)3 FOR MAX OVER CURRENT
 PROTECTION FOR A RECEPTACLE DEVICE.
  
 G) PLEASE SEE UPPER RIGHT HAND CORNER OF PLANS WHICH
 STILL INDICATE A 20A /240V CIRCUIT FOR BATHROOM.
  
 H) PLEASE SEE LOAD ON REFRIGERATOR ON LOAD CALCULATIONS
 INDICATE 1500VA, YET, THE AMPERAGE ON THE PANEL
 SCHEDULE ONLY SHOWS 12A'S? PLEASE CORRELATE
  
 I) PLEASE SEE PANEL SCHEDULE IS STILL ONLY SHOWING 18
 CIRCUITS, WHERE PANEL SCHEDULE IS NOTED AS HAVING 24.
 PLEASE SEE THERE ARE TWO SPACES WHICH INDICATE 20A
 BREAKERS BEING INSTALLED, HOWEVER NO LOADS ARE SHOWN.
 IF THESE ARE SPARES, PLEASE INDICATE AS SUCH.
  
 J) PLEASE SEE HOUSE PANEL WHICH IS SHOWING 1500VA FOR
 EACH LIGHTING CIRCUIT, YET PANEL SCHEDULE LOAD IN AMPS
 IS SHOWN MUCH LESS.
 PLEASE SEE TOTAL CONNECTED LOAD AS SHOWN ON PANEL
 SCHEDULE AND THAT OF THE LOAD SHOW IN LOAD CALCULATIONS
 ARE NOT THE SAME.
  
 K) PLEASE SEE RESPONSE LETTER MENTIONS THE DRYER IS NOW
 REMOVED AS SHOWN ON PANEL SCHEDULE AND CIRCUITS FROM
 PREVIOUS PLANS, HOWEVER PLEASE SEE PLANS STILL INDICATE
 240V CIRCUITS TO TWO OF THESE LOCATIONS.PLEASE SEE
 PLANS SHOW 16/18 FOR UNITS FC AND FA. PLEASE CORRELATE
 CIRCUITING ON PLANS WITH THAT OF THE CIRCUITING ON
 PANEL SCHEDULE(S) TYPICAL.
  
 PLEASE CORRELATE ALL OF THE ABOVE.
 310.16, 240.4, 210.11C2, 210.11C3, 220.16, 220. 408.4
 ETC
 FBC ADMIN SECTION 106.1.2, 106.3.5.1.2
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH GAVE 700.12E
 FOR CIRCUITING OF EMERGENCY LIGHTS HOWEVER PLEASE SEE
 THESE ARE BEING SHOWN ON A DEDICATED CIRCUIT. PLEASE
 SEE THE FOLLOWING IS BEING EXTRACTED FROM THE CODE
 EXACTLY WORD FOR WORD.
  
 "THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES."
  
 THESE SECTIONS ARE INTENDED FOR THE EVENT OF THE
 TRIPPING OF A SINGLE BREAKER/OVER CURRENT PROTECTION
 DEVICE WHICH THE NORMAL LIGHTING IS CONNECTED WILL NOT
 LEAVE IN ONE AREA IN TOTAL DARKNESS. PLEASE SEE IF THE
 NORMAL CIRCUIT AS SHOWN WHICH IS HP-1 TRIPS, THE
 EMERGENCY LIGHT FIXTURES WILL NOT COME ON AND LIGHT UP
 ANY EGRESS AREA IN THE EVENT OF AN EMERGENCY FOR
 OCCUPANTS OR FIRE PERSONNEL.
 PLEASE ADJUST CIRCUITING.
  
 PLEASE ALSO SEE NFPA-101 2003 7.9.2.2
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES FOR 210.12
 WHICH REQUIRED CIRCUITING OF ALL OUTLETS IN BEDROOMS.
 THE NOTE MENTIONED NOT ONLY RECEPTACLES ARE TO BE
 PROTECTED. PLEASE SEE SMOKE DEVICES ARE STILL NOT
 SHOWING THE CIRCUITING FOR THIS. PLEASE SEE PLANS.
 PLEASE SEE IF INDEED THESE ARE "SD" SMOKE DETECTORS AS
 SHOWN, THEN BY THE DEFINITIONS IN NFPA-72 THESE ARE
 BEING CONNECTED TO A FIRE ALARM SYSTEM WHICH WOULD BE
 LOW VOLTAGE WHICH IS NOT SHOWN.
 IF THESE ARE 110/120V UNITS AND THEY ARE DETECTION AND
 ALARM DEVICES, THESE WOULD BE "SA" FOR SMOKE ALARMS PER
 NFPA-72 DEFINITIONS AND WOULD BE REQUIRED TO CIRCUIT TO
 OTHER ARC FAULT PROTECTED CIRCUIT(S) AS SHOWN.
  
 5) NOTE: PLEASE SEE RISER HAS NOW BEEN REVISED SHOWING
 "EQUIPMENT GROUNDING CONDUCTORS" BEING INSTALLED FROM
 THE GUTTER TO EACH OF THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE THIS WAS NOT PART OF THE PREVIOUS REVIEW
 NOTES AS THIS EQUIPMENT GROUNDING CONDUCTOR WAS NOT
 SHOWN ON RISER AS IT IS NOW. PLEASE SEE 250.6 AND
 250.24B AS THIS CONDUCTOR IS ONLY TO BE INSTALLED AFTER
 THE FIRST MEANS OF DISCONNECT. PLEASE SEE THE FOLLOWING
 IS EXTRACTED FROM THE CODE WORD FOR WORD.
 250.6 OBJECTIONABLE CURRENT OVER GROUNDING CONDUCTORS.
 (A) ARRANGEMENT TO PREVENT OBJECTIONABLE CURRENT. THE
 GROUNDING OF ELECTRICAL SYSTEMS, CIRCUIT CONDUCTORS,
 SURGE ARRESTERS, AND CONDUCTIVE NON-CURRENT-CARRYING
 MATERIALS AND EQUIPMENT SHALL BE INSTALLED AND ARRANGED
 IN A MANNER THAT WILL PREVENT OBJECTIONABLE CURRENT
 OVER THE GROUNDING CONDUCTORS OR GROUNDING PATHS.
 250.24
 (B) GROUNDED CONDUCTOR BROUGHT TO SERVICE EQUIPMENT.
 WHERE AN AC SYSTEM OPERATING AT LESS THAN 1000 VOLTS IS
 GROUNDED AT ANY POINT, THE GROUNDED CONDUCTOR(S) SHALL
 BE RUN TO EACH SERVICE DISCONNECTING MEANS AND SHALL BE
 BONDED TO EACH DISCONNECTING MEANS ENCLOSURE. THE
 GROUNDED CONDUCTOR(S) SHALL BE INSTALLED IN ACCORDANCE
 WITH 250.24(B)(1) THROUGH (B)(3).
  
 6) NOTE: PLEASE SEE PREVIOUS REVIEW REQUESTED A LETTER,
 SIGNED, DATED, SEALED AND NOTARIZED LETTER PER FS
 117.05 FOR SIGNATURE VERIFICATION AS PLANS CONTAINED
 WHAT APPEARED TO BE INITIALS AND RESPONSE LETTERS
 CONTAINED A COMPLETELY DIFFERENT SIGNATURE FOR THE
 DESIGNER OF RECORD. PLEASE SEE RESPONSE LETTER MENTIONS
 THE DESIGNER OF RECORD WOULD NOW SIGN PLANS WITH LEGAL
 SIGNATURE, HOWEVER PLEASE SEE SOME SHEETS STILL CONTAIN
 THE OLD ?INITIALS?.
 PLEASE SEE FS 471.025, FAC 61G15-23.002.
 PLEASE SUBMIT LETTER AS PREVIOUSLY REQUESTED AS IT WILL
 BE PLACED IN OUR SIGNATURE FILE FOR FUTURE REFERENCE.
  
 7) NOTE: PLEASE SEE A "DUPLICATE" PERMIT APPLICATION IS
 NOW SUBMITTED IN PACKAGE; HOWEVER PLEASE SEE THAT NOT
 ALL THE SUB CONTRACTORS ARE SIGNED ON APPLICATION AS
 SIGNED ON ORIGINAL PERMIT APPLICATION.
 PLEASE SEE MISSING ELECTRICAL CONTRACTOR WHICH WAS J
 LINN ELECTRIC INC.
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]