| 2006-12-24 18:33:08 | *** UNSAT 6TH REVIEW *** |
| | |
| | |
| | *** PLEASE SEE THAT SOME COMMENTS FROM PREVIOUS REVIEWS |
| | HAVE STILL NOT BEEN ADDRESSED. |
| | PLEASE SEE COMMENTS BELOW. |
| | IT IS GOING TO BE THE ATTEMPT OF THIS REVIEW TO TRY AND |
| | INDICATE EVERY ITEM AS THE RESPONSE LETTER SEEMS TO |
| | LEND TO MISUNDERSTANDING OF THE COMMENTS OR THE CODE |
| | SECTIONS GIVEN. |
| | |
| | ** PLEASE KNOW THAT TO DATE OF THIS REVIEW NO CONTACT |
| | HAS BEEN MADE BY THE DESIGNER OR DESIGN TEAM TO GO OVER |
| | NOTES FOR QUESTIONS OR COMMENTS. |
| | AT THE END OF EACH PREVIOUS REVIEW THIS REVIEWER HAS |
| | PLACED THE DIRECT PHONE NUMBER AND E-MAIL ADDRESS FOR |
| | THIS PURPOSE. |
| | |
| | 1) NOTE: PLEASE KNOW A 4X TIME FEE FOR THE PLAN REVIEW |
| | PORTION OF THE PERMIT FEE HAS NOW BEEN ASSESSED TO THE |
| | DESIGNER OF RECORD DUE TO COMMENTS BEING REPEAT |
| | COMMENTS FOR CODE COMPLIANCE.A NOTICE TO FLORIDA |
| | STATUTES 553.80(2)(B) WAS GIVEN ON PREVIOUS REVIEW. |
| | PLEASE KNOW THAT THE FEE OF $1,359.60 IS DUE BEFORE |
| | PLANS MAY BE RESUBMITTED AND IS THE RESPONSIBILITY OF |
| | THE DESIGNER OF RECORD FOR ELECTRICAL. THIS IS NOT |
| | ASSESSED TO THE CONTRACTOR OR OWNER OF RECORD. PLEASE |
| | ALSO KNOW PLANS ARE BEING RETAINED BY THIS OFFICE ONCE |
| | AGAIN AND NOW MAY BE TURNED INTO THE FLORIDA BOARD OF |
| | PROFESSIONAL ENGINEERS FOR REVIEW. |
| | |
| | 2) NOTE: PLEASE CORRELATE ALL LOADS ON PANEL SCHEDULES |
| | AND LOAD CALCULATIONS SUBMITTED. PLEASE SEE THIS |
| | COMMENT HAS BEEN MADE ON EACH OF THE PREVIOUS REVIEWS. |
| | |
| | A) PLEASE SEE THE PANEL SCHEDULE AT THE TOP MENTIONS |
| | "LOAD IN (AMPS)" HOWEVER THIS SEEMS TO BE IMPOSSIBLE AS |
| | SHOWN. SOME SHOWN IN AMPS, AND OTHER SHOWN IN VA. |
| | |
| | B) PLEASE SEE FOR INSTANCE THE LOAD FOR THE RANGE IS |
| | SHOWN AT 40A?S, HOWEVER THIS DOES NOT CORRELATE WITH |
| | THE VA IN LOAD CALCULATIONS. |
| | |
| | C) PLEASE SEE SEVERAL OTHER CIRCUITS WHICH LOADS ARE |
| | SHOWN IN AMPS WHICH IS OK, HOWEVER THE AMPERAGE AS |
| | SHOWN NEEDS TO CORRELATE WITH THE VA SHOWN IN THE LOAD |
| | CALCULATIONS TO THE LET OF THE PANEL SCHEDULE. |
| | |
| | D) PLEASE THEN SEE SOME LOADS ON PANEL SCHEDULE ARE |
| | BEING SHOWN IN WHAT APPEARS TO BE THE VA FOR EACH |
| | CIRCUIT. (EXAMPLE, PLEASE SEE SMALL APPLIANCE CIRCUITS |
| | SHOWN AT 1.5? ARE THESE AMPS AS NOTED ON PANEL SCHEDULE |
| | OR THE ACTUAL VA, WHICH IS 1500VA? PLEASE ALSO SEE BATH |
| | ROOM CIRCUIT ETC. |
| | |
| | E) PLEASE SEE TOTAL CONNECTED LOAD ON PANEL SCHEDULE |
| | SHOWS 20.8, YET LOAD CALCULATIONS INDICATE 19,768. |
| | |
| | F) PLEASE SEE WASHER IS STILL BEING SHOWN ON A SINGLE |
| | POLE 30A CIRCUIT WITH #10 AWG, YET PLEASE SEE UPPER |
| | PLANS WHICH MENTION A 10AMP CIRCUIT FOR WASHER? (THE |
| | MINIMUM REQUIRED AND LOADS NEED TO CORRELATE FOR THIS. |
| | PLEASE ALSO SEE 210.21(B)3 FOR MAX OVER CURRENT |
| | PROTECTION FOR A RECEPTACLE DEVICE. |
| | |
| | G) PLEASE SEE UPPER RIGHT HAND CORNER OF PLANS WHICH |
| | STILL INDICATE A 20A /240V CIRCUIT FOR BATHROOM. |
| | |
| | H) PLEASE SEE LOAD ON REFRIGERATOR ON LOAD CALCULATIONS |
| | INDICATE 1500VA, YET, THE AMPERAGE ON THE PANEL |
| | SCHEDULE ONLY SHOWS 12A'S? PLEASE CORRELATE |
| | |
| | I) PLEASE SEE PANEL SCHEDULE IS STILL ONLY SHOWING 18 |
| | CIRCUITS, WHERE PANEL SCHEDULE IS NOTED AS HAVING 24. |
| | PLEASE SEE THERE ARE TWO SPACES WHICH INDICATE 20A |
| | BREAKERS BEING INSTALLED, HOWEVER NO LOADS ARE SHOWN. |
| | IF THESE ARE SPARES, PLEASE INDICATE AS SUCH. |
| | |
| | J) PLEASE SEE HOUSE PANEL WHICH IS SHOWING 1500VA FOR |
| | EACH LIGHTING CIRCUIT, YET PANEL SCHEDULE LOAD IN AMPS |
| | IS SHOWN MUCH LESS. |
| | PLEASE SEE TOTAL CONNECTED LOAD AS SHOWN ON PANEL |
| | SCHEDULE AND THAT OF THE LOAD SHOW IN LOAD CALCULATIONS |
| | ARE NOT THE SAME. |
| | |
| | K) PLEASE SEE RESPONSE LETTER MENTIONS THE DRYER IS NOW |
| | REMOVED AS SHOWN ON PANEL SCHEDULE AND CIRCUITS FROM |
| | PREVIOUS PLANS, HOWEVER PLEASE SEE PLANS STILL INDICATE |
| | 240V CIRCUITS TO TWO OF THESE LOCATIONS.PLEASE SEE |
| | PLANS SHOW 16/18 FOR UNITS FC AND FA. PLEASE CORRELATE |
| | CIRCUITING ON PLANS WITH THAT OF THE CIRCUITING ON |
| | PANEL SCHEDULE(S) TYPICAL. |
| | |
| | PLEASE CORRELATE ALL OF THE ABOVE. |
| | 310.16, 240.4, 210.11C2, 210.11C3, 220.16, 220. 408.4 |
| | ETC |
| | FBC ADMIN SECTION 106.1.2, 106.3.5.1.2 |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH GAVE 700.12E |
| | FOR CIRCUITING OF EMERGENCY LIGHTS HOWEVER PLEASE SEE |
| | THESE ARE BEING SHOWN ON A DEDICATED CIRCUIT. PLEASE |
| | SEE THE FOLLOWING IS BEING EXTRACTED FROM THE CODE |
| | EXACTLY WORD FOR WORD. |
| | |
| | "THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE |
| | THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES." |
| | |
| | THESE SECTIONS ARE INTENDED FOR THE EVENT OF THE |
| | TRIPPING OF A SINGLE BREAKER/OVER CURRENT PROTECTION |
| | DEVICE WHICH THE NORMAL LIGHTING IS CONNECTED WILL NOT |
| | LEAVE IN ONE AREA IN TOTAL DARKNESS. PLEASE SEE IF THE |
| | NORMAL CIRCUIT AS SHOWN WHICH IS HP-1 TRIPS, THE |
| | EMERGENCY LIGHT FIXTURES WILL NOT COME ON AND LIGHT UP |
| | ANY EGRESS AREA IN THE EVENT OF AN EMERGENCY FOR |
| | OCCUPANTS OR FIRE PERSONNEL. |
| | PLEASE ADJUST CIRCUITING. |
| | |
| | PLEASE ALSO SEE NFPA-101 2003 7.9.2.2 |
| | |
| | 4) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES FOR 210.12 |
| | WHICH REQUIRED CIRCUITING OF ALL OUTLETS IN BEDROOMS. |
| | THE NOTE MENTIONED NOT ONLY RECEPTACLES ARE TO BE |
| | PROTECTED. PLEASE SEE SMOKE DEVICES ARE STILL NOT |
| | SHOWING THE CIRCUITING FOR THIS. PLEASE SEE PLANS. |
| | PLEASE SEE IF INDEED THESE ARE "SD" SMOKE DETECTORS AS |
| | SHOWN, THEN BY THE DEFINITIONS IN NFPA-72 THESE ARE |
| | BEING CONNECTED TO A FIRE ALARM SYSTEM WHICH WOULD BE |
| | LOW VOLTAGE WHICH IS NOT SHOWN. |
| | IF THESE ARE 110/120V UNITS AND THEY ARE DETECTION AND |
| | ALARM DEVICES, THESE WOULD BE "SA" FOR SMOKE ALARMS PER |
| | NFPA-72 DEFINITIONS AND WOULD BE REQUIRED TO CIRCUIT TO |
| | OTHER ARC FAULT PROTECTED CIRCUIT(S) AS SHOWN. |
| | |
| | 5) NOTE: PLEASE SEE RISER HAS NOW BEEN REVISED SHOWING |
| | "EQUIPMENT GROUNDING CONDUCTORS" BEING INSTALLED FROM |
| | THE GUTTER TO EACH OF THE FIRST MEANS OF DISCONNECT. |
| | PLEASE SEE THIS WAS NOT PART OF THE PREVIOUS REVIEW |
| | NOTES AS THIS EQUIPMENT GROUNDING CONDUCTOR WAS NOT |
| | SHOWN ON RISER AS IT IS NOW. PLEASE SEE 250.6 AND |
| | 250.24B AS THIS CONDUCTOR IS ONLY TO BE INSTALLED AFTER |
| | THE FIRST MEANS OF DISCONNECT. PLEASE SEE THE FOLLOWING |
| | IS EXTRACTED FROM THE CODE WORD FOR WORD. |
| | 250.6 OBJECTIONABLE CURRENT OVER GROUNDING CONDUCTORS. |
| | (A) ARRANGEMENT TO PREVENT OBJECTIONABLE CURRENT. THE |
| | GROUNDING OF ELECTRICAL SYSTEMS, CIRCUIT CONDUCTORS, |
| | SURGE ARRESTERS, AND CONDUCTIVE NON-CURRENT-CARRYING |
| | MATERIALS AND EQUIPMENT SHALL BE INSTALLED AND ARRANGED |
| | IN A MANNER THAT WILL PREVENT OBJECTIONABLE CURRENT |
| | OVER THE GROUNDING CONDUCTORS OR GROUNDING PATHS. |
| | 250.24 |
| | (B) GROUNDED CONDUCTOR BROUGHT TO SERVICE EQUIPMENT. |
| | WHERE AN AC SYSTEM OPERATING AT LESS THAN 1000 VOLTS IS |
| | GROUNDED AT ANY POINT, THE GROUNDED CONDUCTOR(S) SHALL |
| | BE RUN TO EACH SERVICE DISCONNECTING MEANS AND SHALL BE |
| | BONDED TO EACH DISCONNECTING MEANS ENCLOSURE. THE |
| | GROUNDED CONDUCTOR(S) SHALL BE INSTALLED IN ACCORDANCE |
| | WITH 250.24(B)(1) THROUGH (B)(3). |
| | |
| | 6) NOTE: PLEASE SEE PREVIOUS REVIEW REQUESTED A LETTER, |
| | SIGNED, DATED, SEALED AND NOTARIZED LETTER PER FS |
| | 117.05 FOR SIGNATURE VERIFICATION AS PLANS CONTAINED |
| | WHAT APPEARED TO BE INITIALS AND RESPONSE LETTERS |
| | CONTAINED A COMPLETELY DIFFERENT SIGNATURE FOR THE |
| | DESIGNER OF RECORD. PLEASE SEE RESPONSE LETTER MENTIONS |
| | THE DESIGNER OF RECORD WOULD NOW SIGN PLANS WITH LEGAL |
| | SIGNATURE, HOWEVER PLEASE SEE SOME SHEETS STILL CONTAIN |
| | THE OLD ?INITIALS?. |
| | PLEASE SEE FS 471.025, FAC 61G15-23.002. |
| | PLEASE SUBMIT LETTER AS PREVIOUSLY REQUESTED AS IT WILL |
| | BE PLACED IN OUR SIGNATURE FILE FOR FUTURE REFERENCE. |
| | |
| | 7) NOTE: PLEASE SEE A "DUPLICATE" PERMIT APPLICATION IS |
| | NOW SUBMITTED IN PACKAGE; HOWEVER PLEASE SEE THAT NOT |
| | ALL THE SUB CONTRACTORS ARE SIGNED ON APPLICATION AS |
| | SIGNED ON ORIGINAL PERMIT APPLICATION. |
| | PLEASE SEE MISSING ELECTRICAL CONTRACTOR WHICH WAS J |
| | LINN ELECTRIC INC. |
| | |
| | ** ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |