| Plan Review Notes For Permit 05080077 |
| Permit Number |
05080077 |
|
| Review Stop |
P |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2006-11-17 07:41:52 | DENIED; | | | 1. AUTOMATIC CLOTHES WASHERS ARE NOT SHOWN ON FLOOR | | | PLAN, PAGE A-1 AND A-2. PLEASE ADD. | | | 2. AUTOMATIC CLOTHES WASHERS BRANCH DRAIN IS REQUIRED | | | TO BE 3". FBC-2004 PLUMBING SECTION 406.3. | | | 3. PLEASE SIZE ALL PIPING ON RISER DIAGRAMS. | | | 4. ENGINEER IS REQUIRED TO SIGN PLANS NOT INITIAL. | | | 5. WATER RISER DIAGRAM PAGE P-2. WATER HAMMER ARRESTORS | | | ARE REQUIRED AT THE AUTOMATIC CLOTHES WASHERS. PLEASE | | | SHOW ON DRAWING. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|