2006-11-15 14:22:02******** UNSAT 5TH REVIEW ********
  
 *** PLEASE SEE THAT THERE ARE MANY COMMENTS FROM
 PREVIOUS REVIEW WHICH ARE STILL IN NEED OF ADDRESSING
 ALONG WITH SOME NEW COMMENTS BASED ON PLANS SUBMITTED
 WHICH CONTAIN DIFFERENT ITEMS FROM THE PREVIOUS
 REVIEW.
 THIS IS THE 5TH REVIEW, HOWEVER THE 2ND REVIEW FOR THIS
 NEW DESIGNER OF RECORD.
  
 *** PLEASE SEE COMMENTS BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH EITHER AND "OK" OR A "NO" WITH
 FURTHER EXPLANATION ADDED.
 PLEASE SEE SOME COMMENTS MAY BE LABELED OK/NO, AS PART
 OF THE COMMENT MAY HAVE BEEN ADDRESSED AND PART OF THE
 COMMENT MAY NOT HAVE BEEN ADDRESSED.
  
 **PLEASE SEE ANY COMPLETELY NEW NOTES WILL BE ADDED TO
 THE END OF THESE NOTES AND LABELED "NEW NOTES 5TH
 REVIEW".
  
 ** PLEASE KNOW THAT TO DATE OF THIS REVIEW NO ONE HAS
 CONTACTED THIS REVIEWER TO GO OVER ANY COMMENTS OR HAVE
 MADE ANY INQUIRIES IF ANY OF THE COMMENTS WERE NOT
 UNDERSTOOD IN ANY FASHION.
  
 1) NOTE:NO, PLEASE SEE THE ORIGINAL PERMIT
 APPLICATION HAS STILL NOT BEEN SUBMITTED BACK. WE DO
 NOT KEEP THE APPLICATIONS ARE THEY ARE RETURNED WITH
 THE PLANS WHEN THEY ARE PICKED UP. PLEASE KNOW THAT IN
 WORST CASE SCENARIO, A NEW PERMIT APPLICATION MAY BE
 FILLED OUT AND SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #4**
 PLEASE SEE THE PERMIT APPLICATION SUBMITTED BACK IN
 FACT A PHOTO-COPY OF THE ORIGINAL APPLICATION. MUST
 SUBMIT THE ORIGINAL APPLICATION FOR PROCESSING AND
 PERMITTING OF PROJECT.
  
 2) NOTE: OK.
  
 3) NOTE:NO, PLEASE SEE THE RESPONSE LETTER MENTIONS
 THE PLANS WILL NOW BE SIGNED WITH THE ENGINEER'S LEGAL
 SIGNATURE AND NOT INITIALS; HOWEVER PLEASE SEE THE
 PLANS DO NOT STILL SEEM TO INDICATE INITIALS. PLEASE
 SEE THE RESPONSE LETTER WHICH IS "SIGNED" FROM THE
 ENGINEER OF RECORD CONTAINS A COMPLETELY DIFFERENT
 SIGNATURE OF THAT ON PLANS.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #4**
 PLEASE SEE FS 471.025 AS THIS REQUIRES THE PLANS TO BE
 SIGNED WITH LEGAL SIGNATURE. PLANS SEEM BE SIGNED WITH
 WHAT APPEARS TO BE INITIALS, IF INDEED THIS IS THE
 LEGAL SIGNATURE, PLEASE PROVIDE A SIGNED, DATED AND
 SEALED LETTER FOR VERIFICATION. LETTER IS ALSO REQUIRED
 TO BE PROPERLY NOTARIZED UNDER FS 117.05.
 PLEASE KNOW THIS WILL BE PLACED IN OUR SIGNATURE FILE
 FOR ANY FURTHER REFERENCE.
  
 4) NOTE: NO, PLEASE SEE PANEL SCHEDULE(S) AND LOAD
 CALCULATIONS NOW INDICATE TWO SMALL APPLIANCE CIRCUITS;
 HOWEVER THE 2ND SMALL APPLIANCE CIRCUIT IS LOCATED
 FEEDING THE LIVING ROOM RECEPTACLES. PLEASE SEE
 250.52B1, AS THIS IS NOT PERMITTED. PLEASE SEE THE SAME
 CODE ARTICLE GIVEN WHICH DEPICTS THE LOCATIONS
 PERMITTED AND MAY NOT FEED ANY OTHER AREAS. PLEASE ALSO
 SEE ONE OF THE SMALL APPLIANCE CIRCUITS ALSO FEEDS GFI
 RECEPTACLES LOCATED OUTSIDE WHICH IS ALSO NOT
 PERMITTED.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #4**
 PLEASE SEE MISSING TWO MINIMUM SMALL APPLIANCE CIRCUITS
 FROM PLANS, AND PANEL SCHEDULES, ALTHOUGH THESE ARE
 NOTED IN LOAD CALCULATIONS??
 PLEASE SEE 210.52B1,210.11C1,220.16
  
 5) NOTE: OK.
  
 6) NOTE: OK, THE DISHWASHERS WERE REMOVED FROM PLANS
 AND IN RESPONSE LETTER HOWEVER SEE NEW NOTES.
  
 7) NOTE:OK, HOWEVER SEE NEW NOTES PERTAINING TO
 CIRCUITING AND DESIGNATIONS ON PLANS.
  
 ** PREVIOUS REVIEW NOTE FROM 4TH REVIEW **
 PLEASE LIST ARC FAULT PROTECTION ON THE PANEL SCHEDULE
 FOR ALL OUTLET LOCATED ON BEDROOMS. PLEASE SEE 2002 NEC
 210.12, WHICH REQUIRES AFP FOR ALL, NOT ONLY RECEPTS AS
 SHOWN ON PLANS.
  
 8) NOTE: OK, A/C'S REMOVED.
  
 9) NOTE: NO, PLEASE SEE THE TOTAL LOADS SHOWN ON PANEL
 SCHEDULES STILL DO NOT CORRELATE WITH THE LOAD
 CALCULATIONS AS SHOWN.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #4**
 PLEASE SEE NEC FOR LOAD CALCULATIONS. PLEASE SEE TOTAL
 ON PANEL SCHEDULES DO NOT CORRELATE WITH CALCULATIONS.
 PLEASE SEE DE-RATING TWICE IS NOT PERMITTED. THE TOTAL
 LOAD ON EACH PANEL MAY BE DE-RATED FOR PANEL, BUT NOT
 FOR TOTALS FOR THE TABLE DE-RATINGS IN 220.32. PLEASE
 SEE THE HOUSE LOADS ARE TO BE SHOWN SEPARATELY, AND
 ADDED TO TOTAL.
 PLEASE SEE NEC 220, ALL.
 PLEASE SEE ALL OTHER COMMENTS AS THE LOADS WILL BE
 CHANGING.
 215.5, 220,
 FBC ADMIN SECT 106.1.2
  
 10) NOTE: OK.
  
 11) NOTE: OK.
  
 12) NOTE: OK/ NO. PLEASE SEE A NOTE WAS ADJUSTED AND
 NOW READS "FOOTER-STEEL IF AVAILABLE". PLEASE KNOW THIS
 IS OK, HOWEVER AS NOTED IN THE PREVIOUS REVIEW NOTE;
 PLEASE SEE THAT THE CODES BEING REFERENCED ARE NOT FROM
 THE 2002 NEC (NFPA-70) AND DO NOT MATCH WITH THE
 REQUIREMENTS OF THE GROUNDING ELECTRODE SYSTEM. PLEASE
 BE SURE TO SEE THE 2002 AS THE STATE OF FLORIDA HAS NOT
 YET ADOPTED THE 2005 NEC.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #4**
 PLEASE SEE GROUNDING ELECTRODE RISER INDICATE FOOTER
 STEEL TO BE PART OF THE GE SYSTEM?
 PLEASE KNOW IN NEW CONSTRUCTION IT IS AVAILABLE AND IS
 REQUIRED TO BE A PART OF THE SYSTEM, HOWEVER PLEASE SEE
 THAT THIS IS AN EXISTING BUILDING AND ATTACHING TO THE
 EXISTING FOOTER IS NOT REQUIRED, HOWEVER MAY BE DONE.
 PLEASE KNOW, THIS MAY AFFECT THE STRUCTURAL INTEGRITY
 OF THE EXISTING.
 ** PLEASE SEE THE NEC CODES BEING REFERENCE ARE NOT
 FROM THE CURRENT NEC 2002. PLEASE REVISE.
 PLEASE KNOW, SINCE EXISTING FOOTER STEEL CAN NOT BE
 VERIFIED EVEN IF THE ATTACHMENT IS MADE, A MIN OF TWO
 GROUND RODS WILL BE REQUIRED.
 250.50, 250.56
  
 13) NOTE: NO, PLEASE SEE NO PHOTO-METRICS WERE
 SUBMITTED OR ANY LIGHTING LEVELS SHOWN.
 PLEASE ALSO SEE THAT NOW THAT LIGHTING HAS BEEN ADDED
 PLEASE SEE NEW NOTES FOR THIS REVIEW WITH RESPECT TO
 CIRCUITING AND CONTROL OF THESE NEW LIGHTS ADDED.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #4**
 PLEASE SEE MISSING LIGHTING FOR EGRESS STAIRS PER LS
 101 7.8.1.3,
 7.9.2.2.
 PLEASE NOTE AND SHOW A MIN OF 10FT CANDLES REQUIRED FOR
 STAIRS UNDER NORMAL, AND 1FT CANDLE MIN REQUIRED UNDER
 EMERGENCY POWER.
 PLEASE SHOW.
  
 14) NOTE:NO, PLEASE SEE CIRCUITS ARE ADDED AND SHOWN,
 HOWEVER AS STATED ON THE PREVIOUS REVIEW NOTE, PLEASE
 KNOW THESE DEDICATED CIRCUIT(S) MUST MEET 210.11C3.
 THERE ARE ONLY TWO WAYS THIS CANE BE DONE. IN EITHER
 CASE, THESE MAY NOT FEED ANY OTHER RECEPTACLES IN ANY
 OTHER AREAS. (OUTSIDE ETC)
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #4**
 PLEASE SEE MISSING THE REQUIRED DEDICATED BATH(S)
 CIRCUIT(S) AS REQUIRED PER 210.52D,210.11C3, MUST BE
 20A AND #12 AWG.
  
 15) NOTE: NO, PLEASE SEE NEW PANEL SCHEDULE WERE
 SUBMITTED, HOWEVER THE CIRCUITS, SPARES AND NUMERICAL
 DESIGNATIONS OF THE PANEL SIZE AND NUMBER OF POLES
 STILL DO NOT CORRELATE. PLEASE ALSO SEE NEW NOTES DUE
 TO THE NEW REVISED PANEL SCHEDULE SUBMITTED AND THE
 NOTES ADDED TO PLANS.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #4**
 PLEASE SEE PLANS INDICATE CIRCUITS WHICH ARE NOT ON
 PANEL SCHEDULE(S). IN FACT, THESE CIRCUITS ON PANEL
 SCHEDULES ARE SHOWN AS SPARES??
 PLEASE ADJUST.
  
 16) NOTE: OK.
  
 17) NOTE: OK/NO. PLEASE SEE THE FIXTURE(S) SEEM TO HAVE
 BEEN MOVED ON TWO OF THE CLOSETS, HOWEVER NOT ALL.
 PLEASE ALSO SEE EVEN OF A FIXTURE HAS BEEN MOVED TO THE
 WALL ABOVE DOOR, AS THE FIXTURE DESCRIPTION IS NOT
 INDICATED ON SYMBOL LEGEND, THEN AT THIS TIME IT IS NOT
 KNOWN WHETHER OR NOT THESE FIXTURE MOVED MEET CODE AS
 OF YET. PLEASE SEE ALL CLOSETS WITH STORAGE CONTAINING
 EASILY IGNITABLE MATERIALS AND COMBUSTIBLES MUST MEET
 THIS SECTION.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #4**
 PLEASE SEE 410.8 FOR THE MINIMUM REQUIRED CLEARANCES
 FOR CLOSET LT'S.
 PLEASE SEE CODE AS A 18" ASSUMED SHELVING LINE IS
 SHOWN.
  
 18) NOTE: OK.
  
 19) NOTE: OK.
  
 20) NOTE: NO, SAME NOTE. PLANS ARE REQUIRED TO SHOW
 SERVICE AS SHOWN ON RISER ON PLANS. PLANS ONLY SHOW ONE
 DISCONNECT AND ONE METER.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #4**
 PLEASE SHOW ALL METERS/MAINS/SERVICE EQUIPMENT ON
 PLANS.
 RISER SEEMS TO NOW INDICATE SERVICE AS EXISTING,
 HOWEVER THIS LOCATION AND BUILDING DOES NOT SEEM THIS
 IS EXISTING, AND /OR FEEDERS AND SEC'S BEING STILL
 INTACT FROM THE PICTURES OF THIS PROJECT.
 THIS SHOULD BE VERIFIED.
 310.16,240.4,215.5, ETC.
  
  
 ******* NEW NOTES FOR REVIEW #5 ************
 THIS IS DUE TO CHANGES IN PLANS SUBMITTED WHICH WERE
 NOT ON PREVIOUS PLANS.
  
 1) NOTE: PLEASE SEE AS LIGHTING HAS BEEN ADDED TO THE
 PLANS FOR EGRESS AS NOTED ABOVE, PLEASE SEE THESE ARE
 REQUIRED TO BE CIRCUITED AND ALL EMERGENCY LIGHTING
 SHALL BE CIRCUITED PER 700.12E. PLEASE SEE A NOTE WAS
 ADDED WHICH MENTIONS THEY ARE CIRCUITED TO THE "SAME
 ROOM"? AS PLANS DO NOT INDICATE ANY ROOM FOR THIS
 PLEASE ADJUST AND CIRCUIT AS REQUIRED.
 PLEASE ALSO SEE PLANS DO NOT INDICATE ANY MEANS OF
 CONTROL FOR THESE LIGHTS. THIS MUST BE AN AUTOMATED
 CONTROL OF SOME SORT. (PHOTOCELL/ASTRONOMICAL TIME
 CLOCK ETC).
 LS-101 NFPA-101 7.8.1.3, 7.9.2.2 ETC.
  
 2) NOTE: PLEASE SEE PLANS NOW INDICATE A HOUSE PANEL ON
 RISER, HOWEVER NO PANEL SCHEDULE WAS SUBMITTED SHOWING
 THE OVER CURRENT PROTECTION DEVICE AND CONDUCTOR SIZES
 ETC.
 PLEASE SUBMIT.
 FBC 106.1.2, 106.3.5.1.2 ADMINISTRATIVE SECTION AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
 NEC 408.4, 240.4, 310.16 ETC.
  
 3) NOTE: PLEASE SEE A NOTE AT THE BOTTOM OF THE LOAD
 CALCULATIONS SUBMITTED NOW CONTAINS A NOTE WHICH
 STATES: ?FEEDER SIZE SHALL BE BASED UPON 175A'S??
 PLEASE CLARIFY THIS NOTE AS IT SEEMS TO BE LOCATED JUST
 BELOW THE CALCULATIONS FOR COMMERCIAL HOUSE PANEL,
 HOWEVER THE HOUSE PANEL IS BEING SHOWN AS 100A?S AND
 SERVICE ENTRANCE CONDUCTORS TAPPED FROM GUTTER ARE
 BASED ON 100A?S.
 THIS NOTE IS UNCLEAR AND IS NOT KNOWN TO THIS REVIEWER
 WHAT IT HAS TO DO WITH ANYTHING AS SUBMITTED AND SHOWN
 ON PLANS.
 FBC ADMIN SECT 106.1.2, NEC 215.5
  
 4) NOTE: PLEASE SEE AS NOTED ABOVE IN NOTE #15, PLEASE
 CORRELATE ALL CIRCUITING AS SHOWN ON PLANS WITH PANEL
 SCHEDULES. PLEASE SEE DESIGNATIONS FOR BEDROOMS WHICH
 SEEM TO BE REVERSED.
 408.4,
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE DRYER IS BEING SHOWN ON TWO SINGLE
 POLE 20AMP CIRCUITS WHERE THE DRYER IS SHOWN AS A 5KW
 UNIT IN LOAD CALCULATIONS. PLEASE ALSO SEE NOTE CLOUDED
 NOTE AREA ON THE UPPER RIGHT HAND CORNER OF THE PLANS
 ON E-2 AND E-2 INDICATE THE REQUIRED CIRCUITS AND THE
 NOTE FOR THE DRYER DOES NOT CORRELATE.
 PLEASE RE-FIGURE THE MINIMUM OVER CURRENT PROTECTION
 FOR THIS AS, 5KW AT 240V IS HIGHER THAN 20A'S AS SHOWN.
 PLEASE ALSO SEE THIS WOULD NOT BE ON TOW 1-POLE
 CIRCUITS.
 240.4, 310.16, 220.18, 422 ETC
  
 6) NOTE: PLEASE SEE RANGE LOAD IS SHOWN AT 33A'S.
 PLEASE SEE 8KW @ 240V'S. MAY GO UP, HOWEVER MAY NOT GO
 DOWN ON THE FINAL OUT COME OF THAT FIGURE WHEN THE
 CALCULATIONS ARE DONE.
 PLEASE SEE 220.31, 220.19 ETC
  
 7) NOTE: PLEASE SEE PANEL SCHEDULE IS LABELED AS
 3-PHASE ON SCHEDULE, YET THE PANEL AND SERVICE IS
 SINGLE PHASE??
 PLEASE SEE PHASE? A, B, C BEING SHOWN??
 PLEASE CORRELATE.
 408.4, 230.70
 FBC 106.1.2
  
 8) NOTE: PLEASE SEE PANEL DESIGNATIONS ON PLANS HAVE
 NOW BEEN CHANGED. PLEASE SEE PLANS INDICATE AN "F" IN
 FRONT OF ALL THE PANELS. (EXAMPLE) FA, FB, FC AND FD,
 YET PANEL SCHEDULE AND CIRCUITING INDICATES A, B, C AND
 D ONLY.
 WHERE DOES THE F COME INTO THE DESIGN?
 NEC 408.4,
 FBC 106.3.5.1.2
  
 9) NOTE: PLEASE SEE NOTE #6 FROM 4TH REVIEW WHICH SPOKE
 OF THE MULTIPLE CIRCUITS FOR THE DISHWASHER, YET THE
 DISHWASHERS WERE REMOVED.
 PLEASE SEE CLOUDED AREA ON UPPER RIGHT HAND SIDE OF
 PLANS WHICH INDICATE CIRCUITS REQUIRED WHICH STILL
 MENTIONS DISHWASHER(S)?
 THIS IS NOT CLEAR AS LETTER MENTIONS REMOVED, YET NOTED
 ON PLANS AS BEING REQUIRED.
 PLEASE CORRELATE AND COMPLETE SCOPE WHICH IS BEING
 DONE.
 408.4, 310.16,
 FBC ADMIN SECTION 106.1.2
  
 10) NOTE: PLEASE SEE COPY OF FLORIDA STATUTES
 553.80(2)(B) WITH RESPECT TO DESIGN PROFESSIONALS AND
 REPEAT COMMENTS.
 PLEASE ALSO KNOW THAT ONE SET OF EACH ELECTRICAL HAVE
 NOW BEEN RETAINED.
  
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. **IF
 THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF THE
 NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE DO
 NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  