| 2006-11-17 09:40:39 | BUILDING PLAN REVIEW |
| | PERMIT: 05080077 |
| | ADD: 542 19TH STREET |
| | CONT: WEST PALM BEACH HOUSING AUTHORITY |
| | TEL: (561)719-2217 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | 5TH REVIEW |
| | ACTION: DENIED |
| | |
| | 1) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 2A) MISSING THE ORIGINAL APPLICATION, THE |
| | DESCRIPTION OF WORK FROM A COPIED PERMIT |
| | APLICATION AND THE SUBMITTAL SHEET |
| | DOESN'T MATCH. THE SUBMITTAL SHEET |
| | INDICATES A COMPLETE CHANGE OF PLANS. |
| | THIS COULD BE TAKEN AS A COMPLETE |
| | RENOVATION OF THE BUILDING, WHAT IS THE |
| | ACTUAL WORK TO BE ACCOMPLISHED UNDER |
| | THIS PERMIT.106.1.2*. ADD INFO. |
| | |
| | 2B) FROM THE MEETING HELD WITH THE CONTRACTOR AND |
| | DESIGN TEAM, THE INTERIOR WALLS ARE CEMENT BLOCK/ |
| | STUCCO |
| | THIS WAS TO BE MENTIONED ON THE PLAN, AS NO DRYWALL |
| | ON INTERIOR WALLS. |
| | NOTE: A-5NOTE# 2 ON INTERIOR FINISHES INDICATES THE |
| | USE |
| | OF CEMENT BOARD USE IN THE TUB WALL AREAS, |
| | IF BLOCK WALLS OCCUR THE USE OF CEMENT BOARD WOULD |
| | NOT BE NEEDED. |
| | THE OTHER ISUE WITH THE USE OF CEMENT BOARD IS USED IN |
| | |
| | CONJUNCTION WITH EITHER WOOD OR METAL STUDS NO MENTION |
| | |
| | TO A VAPIOR BARRIER TO BE USED BEHIND THE CEMENT |
| | BOARD, |
| | THIS STOPS ANY MOISTURE FROM TRAVELING THROUGH THE |
| | WALL |
| | CAUSING FUNGESS ON THE BACK SIDE OF THE DRYWALL. |
| | |
| | 2C)THE OTHER ISSUE THE COPIED PERMIT APPLICATION ALSO |
| | INDICATES |
| | BALCONY SLAB REPAIR, A NOTE ON SHEET A-4 SEE DRAWINGS |
| | BY TECTON |
| | ENGINEERING FOR BALCONY SLAB REPAIRS. NO SUCH DRAWINGS |
| | WERE |
| | INCORPORATED IN THESE PLANS. EITHER CORRECT THE PERMIT |
| | APPLICATION |
| | DESCEPTION OF WORK OR PROVIDE THEINFORMATION TO |
| | BALCONY REPAIRS BEING MADE. |
| | NOTE NO MENTION OF ANY BALCONY RAILINGS BEING REPLACED |
| | UNDER THIS PERMIT. |
| | |
| | 3) AS A RESULT OF THE MEETING WITH THE CONTRACTOR AND |
| | THE DESIGN TEAM A NEW |
| | EXTERIOR WALL SECTION X/A-5 WAS INCORPORATED INTO THE |
| | PLANS. |
| | NOTE OF REFRENCE NOT SHOWN ON THE PLAN.THE PLANS |
| | INDICATE THE USE OF |
| | 5/8" STUCCO ON GALVANIZED WIRE MESH ON 5/8" CDX |
| | PLYWOOD. THE PLANS |
| | DO NOT INDICATE THE GAUGE OF WIRE MESH NOR THE TYPE OF |
| | WIRE MESH TO |
| | BE USED NOR THE SIZE NAIL OR PATERN OF NAILING. |
| | SECTION 2510.3 LATHING AND FURRING FOR CEMENT PLASTER |
| | (STUCCO). INSTALLATION |
| | INDICATES COMPLIANCE WITH ASTM C-1063. |
| | TABLE 3 PROVIDES THE NOMINAL WEIGHT OF THE METAL |
| | PLASTER BASE, SPACING AND TYPE OF |
| | METAL WIRE LATH . |
| | NOTE FOOTNOTE "D" WHERE PLYWOOD IS USED FOR SHEATHING, |
| | METAL PLASTER BASES SHALL BE FURRED AWAY |
| | FROM VERTICAL SUPPORTS OR SOLID SURFACES AT LEAST 1/4" |
| | . SELF FURRING LATH MEETS FURRING REQUIREMENTS ; |
| | EXCEPT, FURRING EXPANDED METAL LATH IS NOT REQUIRED ON |
| | SUPPORTS HAVING A BEARING SURFACE OF 1 5/8" OR LESS. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |
| | |
| | |
| | |
| | |