| 2006-09-23 00:00:00 | PAUL SCHMITZ, PLUMBING PLANS EXAMINER |
| | [email protected] |
| | FBC PLUMBING 2001 |
| | DENIED |
| | 1) SHT P-1 |
| | TABLE 403.1 MINIMUM FACILITIES |
| | ONE AUTOMATIC CLOTHES WASHER CONNECTION |
| | REQUIRED PER UNIT (E) |
| | 2) SHT P-2 |
| | WATER RISER |
| | ?P604.9 WATER HAMMER. THE FLOW VELOCITY |
| | OF THE WATER DISTRIBUTION SYSTEM |
| | SHALL BE CONTROLLED TO REDUCE THE |
| | POSSIBILITY OF WATER HAMMER.A WATER- |
| | HAMMER ARRESTOR SHALL BE INSTALLED WHERE |
| | QUICK-CLOSING VALVES ARE UTILIZED, |
| | UNLESS OTHERWISE APPROVED.THE ARRESTOR |
| | SHALL BE LOCATED WITHIN AN |
| | EFFECTIVE RANGE OF THE QUICK-CLOSING |
| | VALVE.WATER-HAMMER ARRESTORS SHALL |
| | CONFORM TO ASSE 1010.ACCESS SHALL BE |
| | PROVIDED TO WATER-HAMMER ARRESTORS. |
| | 3) SHT P-3 |
| | WATER HEATER DETAIL RELIEF VALVE. |
| | ?P504.7.1 DISCHARGE. THE RELIEF VALVE |
| | SHALL DISCHARGE FULL SIZE TO A |
| | SAFE PLACE OF DISPOSAL SUCH AS THE |
| | FLOOR, OUTSIDE THE BUILDING OR AN |
| | INDIRECT WASTE RECEPTOR.THE |
| | DISCHARGE PIPE SHALL NOT HAVE ANY |
| | TRAPPED |
| | SECTIONS AND SHALL HAVE A VISIBLE AIR |
| | GAP OR AIR GAP FITTING LOCATED IN |
| | THE SAME ROOM AS THE WATER HEATER. |
| | THE DISCHARGE SHALL BE INSTALLED IN A |
| | MANNER THAT DOES NOT CAUSE PERSONAL |
| | INJURY TO OCCUPANTS IN THE IMMEDIATE |
| | AREA OR STRUCTURAL DAMAGE TO THE |
| | BUILDING. |
| | 4) WATER HEATER PAN DRAIM SIZE. |
| | ?P504.8.1 PAN SIZE AND DRAIN. THE PAN |
| | SHALL NOT BE LESS THAN 1-1/2 |
| | INCHES (38 MM) DEEP AND SHALL BE OF |
| | SUFFICIENT SIZE AND SHAPE TO RECEIVE |
| | ALL DRIPPING OR CONDENSATE FROM THE |
| | TANK OR WATER HEATER.THE PAN SHALL |
| | BE DRAINED BY AN INDIRECT WASTE PIPE |
| | HAVING A MINIMUM DIAMETER OF 3/4 |
| | INCH. |
| | |
| | END OF COMMENTS |
| | |