2006-09-23 00:00:00PAUL SCHMITZ, PLUMBING PLANS EXAMINER
 [email protected]
 FBC PLUMBING 2001
 DENIED
 1) SHT P-1
 TABLE 403.1 MINIMUM FACILITIES
 ONE AUTOMATIC CLOTHES WASHER CONNECTION
 REQUIRED PER UNIT (E)
 2) SHT P-2
 WATER RISER
 ?P604.9 WATER HAMMER. THE FLOW VELOCITY
 OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE
 POSSIBILITY OF WATER HAMMER.A WATER-
 HAMMER ARRESTOR SHALL BE INSTALLED WHERE
 QUICK-CLOSING VALVES ARE UTILIZED,
 UNLESS OTHERWISE APPROVED.THE ARRESTOR
 SHALL BE LOCATED WITHIN AN
 EFFECTIVE RANGE OF THE QUICK-CLOSING
 VALVE.WATER-HAMMER ARRESTORS SHALL
 CONFORM TO ASSE 1010.ACCESS SHALL BE
 PROVIDED TO WATER-HAMMER ARRESTORS.
 3) SHT P-3
 WATER HEATER DETAIL RELIEF VALVE.
 ?P504.7.1 DISCHARGE. THE RELIEF VALVE
 SHALL DISCHARGE FULL SIZE TO A
 SAFE PLACE OF DISPOSAL SUCH AS THE
 FLOOR, OUTSIDE THE BUILDING OR AN
 INDIRECT WASTE RECEPTOR.THE
 DISCHARGE PIPE SHALL NOT HAVE ANY
 TRAPPED
 SECTIONS AND SHALL HAVE A VISIBLE AIR
 GAP OR AIR GAP FITTING LOCATED IN
 THE SAME ROOM AS THE WATER HEATER.
 THE DISCHARGE SHALL BE INSTALLED IN A
 MANNER THAT DOES NOT CAUSE PERSONAL
 INJURY TO OCCUPANTS IN THE IMMEDIATE
 AREA OR STRUCTURAL DAMAGE TO THE
 BUILDING.
 4) WATER HEATER PAN DRAIM SIZE.
 ?P504.8.1 PAN SIZE AND DRAIN. THE PAN
 SHALL NOT BE LESS THAN 1-1/2
 INCHES (38 MM) DEEP AND SHALL BE OF
 SUFFICIENT SIZE AND SHAPE TO RECEIVE
 ALL DRIPPING OR CONDENSATE FROM THE
 TANK OR WATER HEATER.THE PAN SHALL
 BE DRAINED BY AN INDIRECT WASTE PIPE
 HAVING A MINIMUM DIAMETER OF 3/4
 INCH.
  
 END OF COMMENTS
  