2006-09-17 00:00:00REVIEW COMMENCED
 ******** UNSAT 4TH REVIEW ********
  
 *** PLEASE SEE COMPLETELY NEW PLANS ARE
 BEING SUBMITTED AND COMMENTS ARE BEING
 TYPED AS NEW ALTHOUGH MANY OF THE SAME
 COMMENT FROM THE PREVIOUS THREE REVIEWS
 ARE THE SAME.
 THESE SUBMITTED PLANS ARE NOW DONE BY A
 NEW DESIGNER OF RECORD.
  
 1) NOTE: PLEASE SEE THE PERMIT
 APPLICATION SUBMITTED BACK IN IN FACT A
 PHOTO-COPY OF THE ORIGINAL APPLICATION.
 MUST SUBMITTED THE ORIGINAL APPLICATION
 FOR PROCESSING AND PERMITTING OF
 PROJECT.
  
 2) NOTE: PLEASE SEE MISSING LICENSE
 INFORMATION REQUIRED ON TITLE BLOCKS FOR ENGINEERING
 FIRM PER FAC 61G15-23.002.
 FS 471.023.
 MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER.
  
 3) NOTE: PLEASE SEE FS 471.025 AS THIS
 REQUIRES THE PLANS TO BE SIGNED WITH
 LEGAL SIGNATURE. PLANS SEEM BE SIGNED
 WITH WHAT APPEARS TO BE INITIALS, IF
 INDEED THIS IS THE LEGAL SIGNATURE,
 PLEASE PROVIDE A SIGNED, DATED AND
 SEALED LETTER FOR VERIFICATION. LETTER
 IS ALSO REQUIRED TO BE PROPERLY
 NOTARIZED UNDER FS 117.05.
 PLEASE KNOW THIS WILL BE PLACED IN OUR
 SIGNATURE FILE FOR ANY FURTHER REFERENCE.
  
 4) NOTE: PLEASE SEE MISSING TWO MINIMUM
 SMALL APPLIANCE CIRCUITS FROM PLANS, AND
 PANEL SCHEDULES, ALTHOUGH THESE ARE
 NOTED IN LOAD CALCULATIONS??
 PLEASE SEE 210.52B1,210.11C1,220.16
  
 5) NOTE: PLEASE SEE THAT ALL
 CIRCUITS/RECEPTS IN AREAS IN
 CONSIDERATION OF 210.52B1, SHALL ALSO BE
 FIGURED. 210.11C1,220.16 PLEASE ADJUST
 CALCS.
  
 6) NOTE: PLEASE SEE UNITS WHICH CIRCUIT
 AND INDICATE MORE THAN ONE RECEPT FOR
 THE DISHWASHER???
 PLEASE SEE ALSO WHERE OF THE TWO
 RECEPTS, SOME ARE SHOWN BOTH AS GFI AND
 SOME UNITS ONLY SHOW ONE??
 PLEASE SEE SOME UNITS ALSO SHOW RECETPS
 LOCATED OUTSIDE ON THE DISHWASHER
 CIRCUIT(S)??
 PLEASE REVISE AND ADJUST ALL.
  
 7) NOTE: PLEASE LIST ARC FAULT
 PROTECTION ON THE PANEL SCHEDULE FOR ALL
 OUTLET LOCATED ON BEDROOMS. PLEASE SEE
 2002 NEC 210.12, WHICH REQUIRES AFP FOR
 ALL, NOT ONLY RECEPTS AS SHOWN ON PLANS.
  
 8) NOTE: PLEASE CLARIFY A/C'S?? PLEASE
 SEE LOAD CALCS ONLY INDICATE 1800VA??
 YET LOAD ON PANEL SCHEDULE IS HIGHER?
 PLEASE VERIFY HEAT / COLLING ETC
 PLEASE ALSO SEE CALCS MENTIONS, "A/C AT
 100% OR", ? WHAT IS THE OR/
 220.31
  
 9) NOTE: PLEASE SEE NEC FOR LOAD
 CALCULATIONS. PLEASE SEE TOTAL ON PANEL
 SCHEDULES DO NOT CORRELATE WITH
 CALCULATIONS. PLEASE SEE DERATING TWICE
 IS NOT PERMITTED. THE TOTAL LOAD ON EACH
 PANEL MAY DERATED FOR PANEL, BUT NOT FOR
 TOTALS FOR THE TABLE DE-RATINGS IN
 220.32
 PLEASE SEE THE HOUSE LOADS ARE TO BE
 SHOWN SEPARATELY, AND ADDED TO TOTAL.
 PLEASE SEE NEC 220, ALL.
 PLEASE SEE ALL OTHER COMMENTS AS THE
 LOADS WILL BE CHANGING.
 215.5, 220,
 FBC ADMIN SECT 106.1.2
  
 10) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW MAINS. 110.9.
 106.1.2 FBC ADMIN SECT.
  
 11) NOTE: PLEASE SEE RISER NOTES FEEDERS
 FROM HOUSE PANEL. WHERE ARE THESE GOING
 ?
 PLEASE VERIFY AND COMPLETE.
 215.5
  
 12) NOTE: PLEASE SEE GROUNDING ELECTRODE
 RISER INDICATE FOOTER STEEL TO BE PART
 OF THE GE SYSTEM?
 PLEASE KNOW IN NEW CONSTRUCTION IT IS
 AVAILABLE AND IS REQUIRED TO BE A PART
 OF THE SYSTEM, HOWEVER PLEASE SEE THAT
 THIS IS AN EXISTING BUILDING AND
 ATTACHING TO THE EXISTING FOOTER IS NOT
 REQUIRED, HOWEVER MAY BE DONE. PLEASE
 KNOW, THIS MAY AFFECT THE STRUCTURAL
 INTEGRITY OF THE EXISTING.
 ** PLEASE SEE THE NEC CODES BEING
 REFERENCE ARE NOT FROM THE CURRENT NEC
 2002. PLEASE REVISE.
 PLEASE KNOW, SINCE EXISTING FOOTER STEEL
 CAN NOT BE VERIFIED EVEN IF THE
 ATTACHMENT IS MADE, A MIN OF TWO GRNDS
 RODS WILL BE REQUIRED.
 250.50, 250.56
  
 13) PLEASE SEE MISSING LIGHTING FOR
 EGRESS STAIRS PER LS 101 7.8.1.3,
 7.9.2.2.
 PLEASE NOTE AND SHOW A MIN OF 10FT
 CANDLES REQUIRED FOR STAIRS UNDER
 NORMAL, AND 1FT CANDLE MIN REQUIRED
 UNDER EM POWER.
 PLEASE SHOW.
  
 14) NOTE: PLEASE SEE MISSING THE
 REQUIRED DEDICATED BATH(S) CIRCUIT(S) AS
 REQUIRED PER 210.52D,210.11C3, MUST BE
 20A AND #12 AWG.
  
 15) NOTE: PLEASE SEE PLANS INDICATE
 CIRCUITS WHICH ARE NOT ON PANEL
 SCHEDULE(S). IN FACT, THESE CIRCUITS ON
 PANEL SCHEDULES ARE SHOWN AS SPARES??
 PLEASE ADJUST.
  
 16) NOTE: PLEASE SEE MISSING DISCONNECT
 FOR HWH, PER 422.31.
  
 17) NOTE: PLEASE SEE 410.8 FOR THE MIN
 REQUIRED CLEARANCES FOR CLOSET LT'S.
 PLEASE SEE CODE AS A 18" ASSUMED
 SHELVING LINE IS SHOWN.
  
 18) NOTE: PLEASE SEE BUILDING REVIEW
 COMMENTS AS THE "S" SHEETS DID NOT GET
 SIGNED, DATED OR SEALED BY THE
 STRUCTURAL ENGINEER AS LISTED.
 THIS IS ONLY NOTED, AND NOT AN
 ELECTRICAL ITEM.
  
 19) NOTE: PLEASE BE SURE THE FOLLOWING
 CODES AT A MINIMUM IS STATED ON THE
 ELECTRICAL PLANS.
 2002 NFPA-70 (NEC), NFPA-101 2003, 2002
 NFPA-72.
  
 20) NOTE: PLEASE SHOW ALL
 METERS/MAINS/SERVICE EQUIPMENT ON PLANS.
 RISER SEEMS TO NOW INDICATE SERVICE AS
 EXISTING, HOWEVER THIS LOCATION AND
 BUILDING DOES NOT SEEM THIS IS EXISTING,
 AND /OR FEEDERS AND SEC'S BEING STILL
 INTACT FROM THE PICTURES OF THIS
 PROJECT.
 THIS SHOULD BE VERIFIED.
 310.16,240.4,215.5, ETC.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  