| Date |
Text |
| 2006-09-17 00:00:00 | REVIEW COMMENCED |
| | ******** UNSAT 4TH REVIEW ******** |
| | |
| | *** PLEASE SEE COMPLETELY NEW PLANS ARE |
| | BEING SUBMITTED AND COMMENTS ARE BEING |
| | TYPED AS NEW ALTHOUGH MANY OF THE SAME |
| | COMMENT FROM THE PREVIOUS THREE REVIEWS |
| | ARE THE SAME. |
| | THESE SUBMITTED PLANS ARE NOW DONE BY A |
| | NEW DESIGNER OF RECORD. |
| | |
| | 1) NOTE: PLEASE SEE THE PERMIT |
| | APPLICATION SUBMITTED BACK IN IN FACT A |
| | PHOTO-COPY OF THE ORIGINAL APPLICATION. |
| | MUST SUBMITTED THE ORIGINAL APPLICATION |
| | FOR PROCESSING AND PERMITTING OF |
| | PROJECT. |
| | |
| | 2) NOTE: PLEASE SEE MISSING LICENSE |
| | INFORMATION REQUIRED ON TITLE BLOCKS FOR ENGINEERING |
| | FIRM PER FAC 61G15-23.002. |
| | FS 471.023. |
| | MISSING CERTIFICATE OF AUTHORIZATION |
| | NUMBER. |
| | |
| | 3) NOTE: PLEASE SEE FS 471.025 AS THIS |
| | REQUIRES THE PLANS TO BE SIGNED WITH |
| | LEGAL SIGNATURE. PLANS SEEM BE SIGNED |
| | WITH WHAT APPEARS TO BE INITIALS, IF |
| | INDEED THIS IS THE LEGAL SIGNATURE, |
| | PLEASE PROVIDE A SIGNED, DATED AND |
| | SEALED LETTER FOR VERIFICATION. LETTER |
| | IS ALSO REQUIRED TO BE PROPERLY |
| | NOTARIZED UNDER FS 117.05. |
| | PLEASE KNOW THIS WILL BE PLACED IN OUR |
| | SIGNATURE FILE FOR ANY FURTHER REFERENCE. |
| | |
| | 4) NOTE: PLEASE SEE MISSING TWO MINIMUM |
| | SMALL APPLIANCE CIRCUITS FROM PLANS, AND |
| | PANEL SCHEDULES, ALTHOUGH THESE ARE |
| | NOTED IN LOAD CALCULATIONS?? |
| | PLEASE SEE 210.52B1,210.11C1,220.16 |
| | |
| | 5) NOTE: PLEASE SEE THAT ALL |
| | CIRCUITS/RECEPTS IN AREAS IN |
| | CONSIDERATION OF 210.52B1, SHALL ALSO BE |
| | FIGURED. 210.11C1,220.16 PLEASE ADJUST |
| | CALCS. |
| | |
| | 6) NOTE: PLEASE SEE UNITS WHICH CIRCUIT |
| | AND INDICATE MORE THAN ONE RECEPT FOR |
| | THE DISHWASHER??? |
| | PLEASE SEE ALSO WHERE OF THE TWO |
| | RECEPTS, SOME ARE SHOWN BOTH AS GFI AND |
| | SOME UNITS ONLY SHOW ONE?? |
| | PLEASE SEE SOME UNITS ALSO SHOW RECETPS |
| | LOCATED OUTSIDE ON THE DISHWASHER |
| | CIRCUIT(S)?? |
| | PLEASE REVISE AND ADJUST ALL. |
| | |
| | 7) NOTE: PLEASE LIST ARC FAULT |
| | PROTECTION ON THE PANEL SCHEDULE FOR ALL |
| | OUTLET LOCATED ON BEDROOMS. PLEASE SEE |
| | 2002 NEC 210.12, WHICH REQUIRES AFP FOR |
| | ALL, NOT ONLY RECEPTS AS SHOWN ON PLANS. |
| | |
| | 8) NOTE: PLEASE CLARIFY A/C'S?? PLEASE |
| | SEE LOAD CALCS ONLY INDICATE 1800VA?? |
| | YET LOAD ON PANEL SCHEDULE IS HIGHER? |
| | PLEASE VERIFY HEAT / COLLING ETC |
| | PLEASE ALSO SEE CALCS MENTIONS, "A/C AT |
| | 100% OR", ? WHAT IS THE OR/ |
| | 220.31 |
| | |
| | 9) NOTE: PLEASE SEE NEC FOR LOAD |
| | CALCULATIONS. PLEASE SEE TOTAL ON PANEL |
| | SCHEDULES DO NOT CORRELATE WITH |
| | CALCULATIONS. PLEASE SEE DERATING TWICE |
| | IS NOT PERMITTED. THE TOTAL LOAD ON EACH |
| | PANEL MAY DERATED FOR PANEL, BUT NOT FOR |
| | TOTALS FOR THE TABLE DE-RATINGS IN |
| | 220.32 |
| | PLEASE SEE THE HOUSE LOADS ARE TO BE |
| | SHOWN SEPARATELY, AND ADDED TO TOTAL. |
| | PLEASE SEE NEC 220, ALL. |
| | PLEASE SEE ALL OTHER COMMENTS AS THE |
| | LOADS WILL BE CHANGING. |
| | 215.5, 220, |
| | FBC ADMIN SECT 106.1.2 |
| | |
| | 10) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW MAINS. 110.9. |
| | 106.1.2 FBC ADMIN SECT. |
| | |
| | 11) NOTE: PLEASE SEE RISER NOTES FEEDERS |
| | FROM HOUSE PANEL. WHERE ARE THESE GOING |
| | ? |
| | PLEASE VERIFY AND COMPLETE. |
| | 215.5 |
| | |
| | 12) NOTE: PLEASE SEE GROUNDING ELECTRODE |
| | RISER INDICATE FOOTER STEEL TO BE PART |
| | OF THE GE SYSTEM? |
| | PLEASE KNOW IN NEW CONSTRUCTION IT IS |
| | AVAILABLE AND IS REQUIRED TO BE A PART |
| | OF THE SYSTEM, HOWEVER PLEASE SEE THAT |
| | THIS IS AN EXISTING BUILDING AND |
| | ATTACHING TO THE EXISTING FOOTER IS NOT |
| | REQUIRED, HOWEVER MAY BE DONE. PLEASE |
| | KNOW, THIS MAY AFFECT THE STRUCTURAL |
| | INTEGRITY OF THE EXISTING. |
| | ** PLEASE SEE THE NEC CODES BEING |
| | REFERENCE ARE NOT FROM THE CURRENT NEC |
| | 2002. PLEASE REVISE. |
| | PLEASE KNOW, SINCE EXISTING FOOTER STEEL |
| | CAN NOT BE VERIFIED EVEN IF THE |
| | ATTACHMENT IS MADE, A MIN OF TWO GRNDS |
| | RODS WILL BE REQUIRED. |
| | 250.50, 250.56 |
| | |
| | 13) PLEASE SEE MISSING LIGHTING FOR |
| | EGRESS STAIRS PER LS 101 7.8.1.3, |
| | 7.9.2.2. |
| | PLEASE NOTE AND SHOW A MIN OF 10FT |
| | CANDLES REQUIRED FOR STAIRS UNDER |
| | NORMAL, AND 1FT CANDLE MIN REQUIRED |
| | UNDER EM POWER. |
| | PLEASE SHOW. |
| | |
| | 14) NOTE: PLEASE SEE MISSING THE |
| | REQUIRED DEDICATED BATH(S) CIRCUIT(S) AS |
| | REQUIRED PER 210.52D,210.11C3, MUST BE |
| | 20A AND #12 AWG. |
| | |
| | 15) NOTE: PLEASE SEE PLANS INDICATE |
| | CIRCUITS WHICH ARE NOT ON PANEL |
| | SCHEDULE(S). IN FACT, THESE CIRCUITS ON |
| | PANEL SCHEDULES ARE SHOWN AS SPARES?? |
| | PLEASE ADJUST. |
| | |
| | 16) NOTE: PLEASE SEE MISSING DISCONNECT |
| | FOR HWH, PER 422.31. |
| | |
| | 17) NOTE: PLEASE SEE 410.8 FOR THE MIN |
| | REQUIRED CLEARANCES FOR CLOSET LT'S. |
| | PLEASE SEE CODE AS A 18" ASSUMED |
| | SHELVING LINE IS SHOWN. |
| | |
| | 18) NOTE: PLEASE SEE BUILDING REVIEW |
| | COMMENTS AS THE "S" SHEETS DID NOT GET |
| | SIGNED, DATED OR SEALED BY THE |
| | STRUCTURAL ENGINEER AS LISTED. |
| | THIS IS ONLY NOTED, AND NOT AN |
| | ELECTRICAL ITEM. |
| | |
| | 19) NOTE: PLEASE BE SURE THE FOLLOWING |
| | CODES AT A MINIMUM IS STATED ON THE |
| | ELECTRICAL PLANS. |
| | 2002 NFPA-70 (NEC), NFPA-101 2003, 2002 |
| | NFPA-72. |
| | |
| | 20) NOTE: PLEASE SHOW ALL |
| | METERS/MAINS/SERVICE EQUIPMENT ON PLANS. |
| | RISER SEEMS TO NOW INDICATE SERVICE AS |
| | EXISTING, HOWEVER THIS LOCATION AND |
| | BUILDING DOES NOT SEEM THIS IS EXISTING, |
| | AND /OR FEEDERS AND SEC'S BEING STILL |
| | INTACT FROM THE PICTURES OF THIS |
| | PROJECT. |
| | THIS SHOULD BE VERIFIED. |
| | 310.16,240.4,215.5, ETC. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| 2006-09-16 00:00:00 | IN ELECTRIC FOR REVIEW. |