| 2006-09-29 00:00:00 | PERMIT: 05080077 |
| | ADD: 542 19TH ST |
| | CONT:WEST PALM BEACH HOUSING |
| | AUTHORITY |
| | TEL: (561)719-2217 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | BUILDING PLAN REVIEW |
| | 4TH REVIEW |
| | ACTION: DENIED |
| | |
| | 1) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| | NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 2) MISSING THE ORIGINAL APPLICATION, THE DESCRIPTION OF |
| | WORK FROM A COPIED PERMIT APLICATION AND THE SUBMITTAL |
| | SHEET |
| | DOESN'T MATCH. THE SUBMITTAL SHEET |
| | INDICATES A COMPLETE CHANGE OF PLANS. |
| | THIS COULD BE TAKEN AS A COMPLETE |
| | RENOVATION OF THE BUILDING, WHAT IS THE |
| | ACTUAL WORK TO BE ACCOMPLISHED UNDER |
| | THIS PERMIT.106.1.2*. ADD INFO. |
| | |
| | 3) SHEET S-1, THE TITLE BLOCK IS SIGNED |
| | AND SEAL BY THE ARCHITECT OF RECORD. |
| | THERE IS ALSO AN AREA FOR THE ENGINEER |
| | OF RECORD TO SIGN, THE PRINTED NAME AND |
| | ENGINEERS LICENSE NUMBER IS ON THIS |
| | SHEET, WHO IS TAKING RESPONSIBLIITY FOR |
| | THIS WORK. |
| | PLANS, SPECIFICATIONS, REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND |
| | BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 4) AGAIN WITH NOT KNOWING WHAT WILL TAKE |
| | PLACE WITH MECHANICAL, THE ELECTRICAL |
| | SHEETS INDICATE A/C 1800 VA, PLEASE |
| | PROVIDE THE APPROPRIATE ENERGY FORMS. |
| | |
| | 5) 2004 FBC |
| | 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING |
| | ASSEMBLIES SEPARATING DWELLING UNITS |
| | FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND |
| | TRANSMISSION CLASS (STC) OF NOT LESS |
| | THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 90. PENETRATIONS |
| | OR OPENINGS IN CONSTRUCTION ASSEMBLIES |
| | FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| | CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR |
| | EXHAUST DUCTS SHALL BE |
| | SEALED, LINED, INSULATED OR OTHERWISE |
| | TREATED TO MAINTAIN THE REQUIRED |
| | RATINGS. THIS REQUIREMENT SHALL NOT |
| | APPLY TO DWELLING UNIT ENTRANCE DOORS; |
| | HOWEVER, SUCH DOORS SHALL BE TIGHT |
| | FITTING TO THE FRAME AND SILL. |
| | |
| | 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING |
| | UNIT AND A PUBLIC OR SERVICE AREA WITHIN |
| | THE STRUCTURE SHALL HAVE AN IMPACT |
| | INSULATION CLASS (IIC) RATING OF NOT |
| | LESS THAN 50 (45 IF FIELD TESTED) WHEN |
| | TESTED IN ACCORDANCE WITH ASTM E 492. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |