Plan Review Notes
Plan Review Notes For Permit 05080077
Permit Number 05080077
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2006-09-22 00:00:00*****UNSAT*****
  
  
  
  
 1.) SHOW/DISPLAY THE ADDRESS ON THE
 STRUCTURE AS WELL AS THE APT/UNIT NUMBER
 OR ALPHABET. AS PER WEST PALM BEACH
 CODE, THE NUMERICAL ADDRESS SHALL BE NO
 LESS THAN 6" IN HEIGHT AND 1" IN WIDTH.
 INDIVIDUAL APARTMENT/UNITS SHALL BE NO
 LESS THAN 3" IN HEIGHT.
  
 2.) CONSTRUCTION AND/OR DEMOLITION
 OPERATIONS SHALL NOT INTERFERE OR HINDER
 EMERGENCY ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF.
  
 3.)ENTRANCES, CORRIDORS, AND EXITS ARE
 TO BE CLEAR AND UNOBSTRUCTED.
  
 4.) INTERIOR WALLS AND CEILING SHALL BE
 CLASS "A" OR CLASS "B".
  
 5.) PLEASE SHOW THE LOCATION OF 2A10BC
 RATED FIRE EXTINGUISHERS, WHETHER
 INTERIOR OR EXTERIOR.
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722