| 2005-12-21 00:00:00 | *********** UNSAT *************** |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW. |
| | |
| | 1)NOTE:PLEASE SEE FS BELOW ,AS SCOPE |
| | OF WORK REQUIRES PLANS TO BE DONE BY ANY |
| | ARCHITECT AT A MIN. |
| | PLEASE ALSO SEE FBC 104.6.3.4.3 WHICH, |
| | WHEN NOT REQUIRED TO BE DONE ANY |
| | ARCHITECT, REQUIRES THE CONTRACTOR |
| | DESIGNING PLANS TO PRINT NAME AND SIGN |
| | ALL SHEETS OF SAID DOCUMENTS. PLEASE SEE |
| | FS 481.229 W |
| | PLEASE SEE ALL COPIES OF ENGINEERING, |
| | PLANS SPECS ETC MUST BE SIGNED, DATED |
| | AND SEALED WITH ORIGINAL SIGNATURE, |
| | RAISED SEAL. PLEASE SEE BLDG REVIEW |
| | COMMENTS FOR ENGINEERING DETAILS |
| | SUBMITTED WHICH ARE PHOTOCOPIES OF |
| | SIGNED AND SEALED DETAILS, |
| | FS 471.025,FAC 61G15-23.002 |
| | |
| | 2)NOTE:OK |
| | |
| | 3)NOTE: OK, HOWEVER SEE NEW NOTE FOR |
| | GROUNDING ELECTRODE CONDUCTOR |
| | |
| | |
| | 4)NOTE: PLEASE SEE SOME EELCTRICAL |
| | DEVICE FOR WHAT APPEARS TO BE ITEMS FROM |
| | HOUSE PANEL, ARE NOT CIRCUITED ON PLANS. |
| | PLEASE SEE REDLINED PLANS. |
| | PLEASE SEE PLANS SEEM TO LABEL ALL UNITS |
| | ARE TYPICAL. |
| | PLEASE SEE NOW AN EGRESS STAIR ETC IS |
| | SHOWN WIHT NEW LTS. |
| | PLEASE SEE LS-101 7.8 WHICH REQUIRES A |
| | MIN OF BATTERY BACK UP LIGHTING TO THE |
| | PUBLIC RIGHT OF WAY. |
| | PLEASE SEE THAT A MIN OF 10 FT CANDLES |
| | UNDER NORMAL POWER IS REQUIRED, MAY BE |
| | RATED AT 1FT CANDLE UNDER EMERGENCY |
| | OWER. |
| | |
| | 5)NOTE:OK |
| | |
| | 6)NOTE:OK |
| | |
| | 7)NOTE: OK, HOWEVER PLEASE SEE TWO BATH |
| | GFI CIRCUITS SHOWN ON PANEL SCHEDULE, |
| | AND PLANS ONLY SHOW ONE BATHRM. |
| | |
| | 8)NOTE: OK |
| | |
| | 9)NOTE: OK |
| | |
| | 10)NOTE: OK |
| | |
| | 11)NOTE: OK |
| | |
| | 12)NOTE: OK |
| | |
| | 13)NOTE: OK |
| | |
| | 14)NOTE: OK |
| | |
| | 15)NOTE:NO, NOTHING COULD BE LOCATED |
| | ON PLANS FOR DEVICES MEETING THESE |
| | REQUIREMENTS. |
| | PLEASE SEE FAIR HOUSING ACT |
| | REGUALTIONS,24 CFR 100.205 FOR MIN |
| | HEIGHTS ON DEVICES AND LOCATIONS. |
| | |
| | NEW NOTE: |
| | 1)NOTE: PLEASE SEE GROUNDING ELECTRODE |
| | CONDUCTOR SHALL BE SIZED ACCORD TO |
| | 250.66 A 1/0 MIN WILL BE REQUIRED FOR |
| | 500MCM. |
| | |
| | PLEASE SEE ANY OTHER POSSIBLE COMMENTS |
| | FROM OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |