| Plan Review Notes For Permit 05080077 |
| Permit Number |
05080077 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-31 00:00:00 | ******DENIED****** | | | | | | 1) PLANS SHOW SMOKE DETECTORS OUTSIDE | | | THE SLEEPING ROOMS. IN ACCORDANCE WITH | | | NFPA 101, SECTION 30.3.4.5.2, SMOKE | | | DETECTORS ARE REQUIRED INSIDE SLEEPING | | | ROOMS IN ADDITION TO OUTSIDE UNLESS THE | | | BUILDING IS FIRE SPRINKLERED. "ANY | | | ALTERATION OR ANY INSTALLATION OF NEW | | | EQUIPMENT SHALL MEET AS NEARLY AS | | | PRACTICABLE, THE REQUIREMENTS FOR NEW | | | CONSTRUCTION", NFPA 101, SECTION 4.6.8. | | | | | | 2) PLEASE SHOW LOCATIONS OF 2A-10B,C | | | RATED FIRE EXTINGUISHERS. INSTALLATION | | | SHALL NOT EXCEED 75' TRAVEL DISTANCE | | | REQUIREMENT. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|