Plan Review Notes
Plan Review Notes For Permit 05080077
Permit Number 05080077
Review Stop E
Sequence Number 1
Notes
Date Text
2005-08-11 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT PLANS FOR COMPLETE
 SCOPE OF WORK BEING DONE. PLEASE SEE FS
 481.229 WHICH REQUIRES PLANS TO BE DONE
 AN ARCHITECT. PLANS MUST BE SIGNED,
 DATED AND SEALED.
 PLEASE SEE ALL COPIES OF ENGINEERING,
 PLANS SPECS ETC MUST BE SIGNED, DATED
 AND SEALED WITH ORIGINAL SIGNATURE,
 RAISED SEAL. PLEASE SEE BLDG REVIEW
 COMMENTS FOR ENGINEERING DETAILS
 SUBMITTED WHICH ARE PHOTOCOPIES OF
 SIGNED AND SEALED DETAILS,
 FS 471.025,FAC 61G15-23.002
  
 2)NOTE: PLEASE SEE CONDUIT FILL FOR 1"
 SCHEDULE 80 PVC IS EXCEEDED WITH
 CONDUCTORS AS SHOWN.
 PLEASE ADJUST.300.17
  
 3)NOTE: PLEASE SEE NOTES MENTION 350 MCM
 IS REATED FOR 350A'S. PLEASE SEE 110.14,
 UNLESS ALL EQUIPMENT , LUGS ETC ARE
 RATED FOR 90 DEGREES, ONLY THE 75 DEGREE
 COL FOR AMPERE RATINGS MAY BE USED.
 PLEASE SEE A 400A RATED SERVICE IS BEING
 SUPPLIED, SEC'S ARE TO BE RATED AT A MIN
 FOR 400A'S. (500MCM)
 240.4,310.16
  
 4)NOTE: PLEASE SUBMIT COMPLETE PLANS
 SHOWING ALL CIRCUITING AND CORRELATE
 WITH PANEL SCHEDULE(S) TO BE SUBMIITED.
 PANEL SCHEDULE SHALL CONTIAN ALL MIN
 CIRCUITING AS REQUIRED PER NEC 2002.
 PLEASE SEE PLANS MISSING WALL AREAS ON
 LOWER UNITS.
 PLEASE SEE PLANS MENTIONS SAME AS ABOVE,
 HOWEVER PLEASE SEE THAT SECOND FLR UNITS
 ARE REQUIRED TO MENAS OF EGRESS LIGHTING
 PER 210.70, LS 101 5-8
  
 5)NOTE: PLEASE SEE PLANS INDICATE GAS
 WATER HEATER AND WALL HEATER, HOWEVER,
 LOAD CALCS INDICATE ELECTRIC??
 PLEASE CORRELATE.
  
 6)NOTE: PLEASE SEE A MIN OF TWO SMALL
 APPLIANCE CIRCUITS ARE REQUIRED. LOAD
 CALCULATION INDICATE TWO, HOWEVER PLANS
 ONLY INDICATE ONEAND ONE CIRCUIT?
 210.52B1,210.11C1,220.16
  
 7)NOTE: PLEASE ALSO INDICATE THE MIN
 DEDICATED BATH(S) CIRCUIT(S).
 210.52D,210.11C3
 MUST BE 20A AND #12.
 PLEASE SEE BATH RM BEING SHOWN ON WITH
 SD'S AND GEN LTS?
  
 8)NOTE: PLEASE SEE 210.11C2, 220.16
 WHICH REQUIRES A MIN OF ONE LAUNDRY
 CIRCUIT. IF GEN FACILITIES ARE SUPPLIED
 PLEASE SHOW ON PLANS.
  
 9)NOTE: PLEASE SEE ALL CONTINUOUS
 "HOUSE" LOADS SHALL BE SHOWN @ 125%.
 215.3.230.42 ETC.
  
 10)NOTE: PLEASE SEE AN EQUIPMENT
 GROUNDING CONDUCTOR IS BEING SHOWN FROM
 METER TO MAINS/FIRST MEANS OF
 DISCONNECT.
 PLEASE SEE 250.6, AN "EQUIPMENT
 GROUNDING" CONDUCTOR IS ONLY AFTER THE
 FIRST MEANS OF DICSONNECT.
 250.24
  
 11)NOTE: PLEASE SEE 410.8 FOR MIN
 CLEARENCE OF CLOST LIGHTING FIXTURES.
  
 12)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 13)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 210.12
  
 14)NOTE: PLEASE SEE RANGE IS SHOWN ON
 LOAD CALCULATIONS, HOWEVER PLANS MENTION
 NIC?
 PLEASE CORRELATE.
  
 15)NOTE: PLEASE SEE FAIR HOUSING ACT
 REGUALTIONS,24 CFR 100.205 FOR MIN
 HEIGHTS ON DEVICES AND LOCATIONS.
 PLEASE SHOW.
  
 PLEASE SEE ANY OTHER POSSIBLE COMMENTS
 FROM OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICLA PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  