| 2005-08-11 00:00:00 | *********** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SUBMIT PLANS FOR COMPLETE |
| | SCOPE OF WORK BEING DONE. PLEASE SEE FS |
| | 481.229 WHICH REQUIRES PLANS TO BE DONE |
| | AN ARCHITECT. PLANS MUST BE SIGNED, |
| | DATED AND SEALED. |
| | PLEASE SEE ALL COPIES OF ENGINEERING, |
| | PLANS SPECS ETC MUST BE SIGNED, DATED |
| | AND SEALED WITH ORIGINAL SIGNATURE, |
| | RAISED SEAL. PLEASE SEE BLDG REVIEW |
| | COMMENTS FOR ENGINEERING DETAILS |
| | SUBMITTED WHICH ARE PHOTOCOPIES OF |
| | SIGNED AND SEALED DETAILS, |
| | FS 471.025,FAC 61G15-23.002 |
| | |
| | 2)NOTE: PLEASE SEE CONDUIT FILL FOR 1" |
| | SCHEDULE 80 PVC IS EXCEEDED WITH |
| | CONDUCTORS AS SHOWN. |
| | PLEASE ADJUST.300.17 |
| | |
| | 3)NOTE: PLEASE SEE NOTES MENTION 350 MCM |
| | IS REATED FOR 350A'S. PLEASE SEE 110.14, |
| | UNLESS ALL EQUIPMENT , LUGS ETC ARE |
| | RATED FOR 90 DEGREES, ONLY THE 75 DEGREE |
| | COL FOR AMPERE RATINGS MAY BE USED. |
| | PLEASE SEE A 400A RATED SERVICE IS BEING |
| | SUPPLIED, SEC'S ARE TO BE RATED AT A MIN |
| | FOR 400A'S. (500MCM) |
| | 240.4,310.16 |
| | |
| | 4)NOTE: PLEASE SUBMIT COMPLETE PLANS |
| | SHOWING ALL CIRCUITING AND CORRELATE |
| | WITH PANEL SCHEDULE(S) TO BE SUBMIITED. |
| | PANEL SCHEDULE SHALL CONTIAN ALL MIN |
| | CIRCUITING AS REQUIRED PER NEC 2002. |
| | PLEASE SEE PLANS MISSING WALL AREAS ON |
| | LOWER UNITS. |
| | PLEASE SEE PLANS MENTIONS SAME AS ABOVE, |
| | HOWEVER PLEASE SEE THAT SECOND FLR UNITS |
| | ARE REQUIRED TO MENAS OF EGRESS LIGHTING |
| | PER 210.70, LS 101 5-8 |
| | |
| | 5)NOTE: PLEASE SEE PLANS INDICATE GAS |
| | WATER HEATER AND WALL HEATER, HOWEVER, |
| | LOAD CALCS INDICATE ELECTRIC?? |
| | PLEASE CORRELATE. |
| | |
| | 6)NOTE: PLEASE SEE A MIN OF TWO SMALL |
| | APPLIANCE CIRCUITS ARE REQUIRED. LOAD |
| | CALCULATION INDICATE TWO, HOWEVER PLANS |
| | ONLY INDICATE ONEAND ONE CIRCUIT? |
| | 210.52B1,210.11C1,220.16 |
| | |
| | 7)NOTE: PLEASE ALSO INDICATE THE MIN |
| | DEDICATED BATH(S) CIRCUIT(S). |
| | 210.52D,210.11C3 |
| | MUST BE 20A AND #12. |
| | PLEASE SEE BATH RM BEING SHOWN ON WITH |
| | SD'S AND GEN LTS? |
| | |
| | 8)NOTE: PLEASE SEE 210.11C2, 220.16 |
| | WHICH REQUIRES A MIN OF ONE LAUNDRY |
| | CIRCUIT. IF GEN FACILITIES ARE SUPPLIED |
| | PLEASE SHOW ON PLANS. |
| | |
| | 9)NOTE: PLEASE SEE ALL CONTINUOUS |
| | "HOUSE" LOADS SHALL BE SHOWN @ 125%. |
| | 215.3.230.42 ETC. |
| | |
| | 10)NOTE: PLEASE SEE AN EQUIPMENT |
| | GROUNDING CONDUCTOR IS BEING SHOWN FROM |
| | METER TO MAINS/FIRST MEANS OF |
| | DISCONNECT. |
| | PLEASE SEE 250.6, AN "EQUIPMENT |
| | GROUNDING" CONDUCTOR IS ONLY AFTER THE |
| | FIRST MEANS OF DICSONNECT. |
| | 250.24 |
| | |
| | 11)NOTE: PLEASE SEE 410.8 FOR MIN |
| | CLEARENCE OF CLOST LIGHTING FIXTURES. |
| | |
| | 12)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 13)NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | 2002 210.12 |
| | |
| | 14)NOTE: PLEASE SEE RANGE IS SHOWN ON |
| | LOAD CALCULATIONS, HOWEVER PLANS MENTION |
| | NIC? |
| | PLEASE CORRELATE. |
| | |
| | 15)NOTE: PLEASE SEE FAIR HOUSING ACT |
| | REGUALTIONS,24 CFR 100.205 FOR MIN |
| | HEIGHTS ON DEVICES AND LOCATIONS. |
| | PLEASE SHOW. |
| | |
| | PLEASE SEE ANY OTHER POSSIBLE COMMENTS |
| | FROM OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICLA PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |