| 2005-08-10 00:00:00 | PAUL SCHMITZ, PLUMBING & GAS PLANS |
| | EXAMINERDENIED |
| | 561-805-6692 |
| | [email protected] |
| | |
| | REVIEW FBC 2001 CH 11 |
| | FLORIDA ACCESIBILITY CODE. |
| | |
| | (1) ?11-4.21 SHOWER STALLS. |
| | ?11-4.21.1 GENERAL. ACCESSIBLE SHOWER |
| | STALLS SHALL COMPLY WITH ?11-4.21. |
| | ?11-4.21.2 SIZE AND CLEARANCES. EXCEPT |
| | AS SPECIFIED IN ?11-9.1.2, SHOWER |
| | STALL SIZE AND CLEAR FLOOR SPACE SHALL |
| | COMPLY WITH FIGURE 11-35(A) OR |
| | FIGURE 11-35(B).THE SHOWER STALL IN |
| | FIGURE 11-35(A) SHALL BE 36 |
| | INCHES BY 36 INCHES (915 MM BY 915 |
| | MM).SHOWER STALLS REQUIRED BY |
| | ?11-9.1.2 SHALL COMPLY WITH FIGURE |
| | 11-57(A) OR FIGURE 11-57(B).THE |
| | SHOWER STALL IN FIGURE 11-35(B) WILL |
| | FIT INTO THE SPACE REQUIRED FOR A |
| | BATHTUB. |
| | ?11-4.21.4 GRAB BARS. GRAB BARS |
| | COMPLYING WITH ?11-4.26 SHALL BE |
| | PROVIDEDAS SHOWN IN FIGURE 11-37. |
| | ?11-4.21.5 CONTROLS. FAUCETS AND OTHER |
| | CONTROLS COMPLYING WITH ?11-4.27.4 |
| | SHALL BE LOCATED AS SHOWN IN FIGURE |
| | 11-37.IN SHOWER STALLS 36 INCHES |
| | BY 36 INCHES (915 MM BY 915 MM), ALL |
| | CONTROLS, FAUCETS, AND THE SHOWER |
| | UNIT SHALL BE MOUNTED ON THE SIDE WALL |
| | OPPOSITE THE SEAT. |
| | ?11-4.21.6 SHOWER UNIT. A SHOWER SPRAY |
| | UNIT WITH A HOSE AT LEAST 60 |
| | INCHES (1525 MM) LONG THAT CAN BE USED |
| | BOTH AS A FIXED SHOWER HEAD AND AS |
| | A HAND-HELD SHOWER SHALL BE PROVIDED. |
| | |
| | (2)?11-4.18 URINALS. |
| | ?11-4.18.1 GENERAL. ACCESSIBLE URINALS |
| | SHALL COMPLY WITH ?11-4.18. |
| | ?11-4.18.2 HEIGHT. URINALS SHALL BE |
| | STALL-TYPE OR WALL-HUNG WITH AN |
| | ELONGATED RIM AT A MAXIMUM OF 17 |
| | INCHES (430 MM) ABOVE THE FINISH FLOOR. |
| | ?11-4.18.3 CLEAR FLOOR SPACE. A CLEAR |
| | FLOOR SPACE 30 INCHES BY 48 INCHES |
| | (760 MM BY 1220 MM) SHALL BE PROVIDED |
| | IN FRONT OF URINALS TO ALLOW FORWARD |
| | APPROACH.THIS CLEAR SPACE SHALL |
| | ADJOIN OR OVERLAP AN ACCESSIBLE ROUTE |
| | AND SHALL COMPLY WITH ?11-4.2.4. |
| | URINAL SHIELDS THAT DO NOT EXTEND BEYOND |
| | THE FRONT EDGE OF THE URINAL RIM MAY BE |
| | PROVIDED WITH 29 INCHES (735 MM) |
| | CLEARANCE BETWEEN THEM. |
| | ?11-4.18.4 FLUSH CONTROLS. FLUSH |
| | CONTROLS SHALL BE HAND OPERATED OR |
| | AUTOMATIC, AND SHALL COMPLY WITH |
| | ?11-4.27.4, AND SHALL BE MOUNTED NO MORE |
| | THAN 44 INCHES (1120 MM) ABOVE THE |
| | FINISH FLOOR. |
| | |
| | (3) 11-4.17 TOILET STALLS. |
| | ?11-4.17.1 LOCATION. ACCESSIBLE TOILET |
| | STALLS SHALL BE ON AN ACCESSIBLE |
| | ROUTE AND SHALL MEET THE REQUIREMENTS |
| | OF ?11-4.17. |
| | ?11-4.17.2 WATER CLOSETS. |
| | WATER CLOSETS IN ACCESSIBLE STALLS SHALL |
| | COMPLY WITH ?11-4.16. |
| | ?11-4.17.3 SIZE AND ARRANGEMENT. THE |
| | SIZE AND ARRANGEMENT OF THE |
| | STANDARD TOILET STALL SHALL COMPLY |
| | WITH FIGURE 11-30(A), STANDARD STALL. |
| | STANDARD TOILET STALLS WITH A MINIMUM |
| | DEPTH OF 56 INCHES (1420 MM) (SEE |
| | FIGURE 11-30(A)) SHALL HAVE |
| | WALL-MOUNTED WATER CLOSETS.IF THE |
| | DEPTH OF A |
| | STANDARD TOILET STALL IS INCREASED AT |
| | LEAST 3 INCHES (75 MM), THEN A |
| | FLOOR-MOUNTED WATER CLOSET MAY BE |
| | USED.ARRANGEMENTS SHOWN FOR STANDARD |
| | TOILET STALLS MAY BE REVERSED TO ALLOW |
| | EITHER A LEFT- OR RIGHT-HAND |
| | APPROACH.ADDITIONAL STALLS SHALL BE |
| | PROVIDED IN CONFORMANCE WITH |
| | ?11-4.22.4 |
| | ?11-4.17.4 TOE CLEARANCES. IN STANDARD |
| | STALLS, THE FRONT PARTITION AND |
| | AT LEAST ONE SIDE PARTITION SHALL |
| | PROVIDE A TOE CLEARANCE OF AT LEAST 9 |
| | INCHES (230 MM) ABOVE THE FLOOR.IF |
| | THE DEPTH OF THE STALL IS GREATER |
| | THAN 60 INCHES (1525 MM), THEN THE TOE |
| | CLEARANCE IS NOT REQUIRED. |
| | ?11-4.17.5 DOORS. |
| | TOILET STALL DOORS, INCLUDING DOOR |
| | HARDWARE, SHALL COMPLY WITH ?11-4.13. |
| | THE DOORS SHALL BE SELF CLOSING.IF |
| | TOILET STALL APPROACH IS FROM LATCH |
| | SIDE OF THE STALL DOOR, CLEARANCE |
| | BETWEEN THE DOOR SIDE OF THE STALL AND |
| | ANY OBSTRUCTION MAY BE REDUCED TO A |
| | MINIMUM OF 42 INCHES (1065 MM) (SEE |
| | FIGURE 11-30).DOORS SHALL NOT SWING |
| | INTO THE CLEAR FLOOR SPACE OF ANY |
| | FIXTURE. |
| | ?11-4.17.6 GRAB BARS. GRAB BARS |
| | COMPLYING WITH THE LENGTH AND |
| | POSITIONING SHOWN IN FIGURE 11-30(A), |
| | FIGURE 11-30(B), FIGURE 11-30(C), |
| | AND FIGURE 11-30(D) SHALL BE PROVIDED. |
| | GRAB BARS MAY BE MOUNTED WITH |
| | ANY DESIRED METHOD AS LONG AS THEY |
| | HAVE A GRIPPING SURFACE AT THE |
| | LOCATIONS SHOWN AND DO NOT OBSTRUCT |
| | THE REQUIRED CLEAR FLOOR AREA.GRAB |
| | BARS SHALL COMPLY WITH ?11-4.26. |
| | |
| | (4) 11-4.22 TOILET ROOMS. |
| | ?11-4.22.1 MINIMUM NUMBER. TOILET |
| | FACILITIES REQUIRED TO BE ACCESSIBLE |
| | BY ?11-4.1 SHALL COMPLY WITH ?11-4.22. |
| | ACCESSIBLE TOILET ROOMS SHALL BE |
| | ON AN ACCESSIBLE ROUTE. |
| | ?11-4.22.2 DOORS. |
| | ?11-4.22.2(1) ALL DOORS TO |
| | ACCESSIBLE TOILET ROOMS SHALL COMPLY |
| | WITH |
| | ?11-4.13.DOORS SHALL NOT SWING |
| | INTO THE CLEAR FLOOR SPACE REQUIRED |
| | FOR ANY FIXTURE. |
| | ?11-4.22.3 CLEAR FLOOR SPACE. THE |
| | ACCESSIBLE FIXTURES AND CONTROLS |
| | REQUIRED IN ?11-4.22.4, ?11-4.22.5, |
| | ?11-4.22.6, AND ?11-4.22.7 SHALL BE |
| | ON AN ACCESSIBLE ROUTE.AN |
| | UNOBSTRUCTED TURNING SPACE COMPLYING |
| | WITH 11-4.2.3 SHALL BE PROVIDED WITHIN |
| | AN ACCESSIBLE TOILET ROOM. |
| | THE CLEAR FLOORSPACE AT FIXTURES AND |
| | CONTROLS, THE ACCESSIBLE ROUTE, AND THE |
| | TURNING |
| | SPACE MAY OVERLAP. |
| | |
| | END OF COMMENTS |
| | |
| | |
| | |
| | |
| | |