| 2005-09-02 00:00:00 | BUILDING REVIEW SECOND CHECKLIST: |
| | 1- ACCORDING TO ANCHOR CHART #7 ON SHEET |
| | 5 OF 5:SOME ANCHORS NEED TO BE SPACED |
| | AT 18"O.C. NOT 24"O.C. (SEE OPENINGS #7 |
| | AND #8) AND REVISE AS REQUIRED. |
| | *INSTALLATION SCHEDULE WAS NOT REVISED |
| | TO REFLECT THIS CHANGE. |
| | |
| | 2- RESPONSE TO COMMENT 2(B) FROM |
| | PREVIOUS CHECKLIST WAS THAT OPENINGS 2 |
| | THRU 6 WERE FOR CONCRETE TOP AND |
| | CONCRETE BLOCK BOTTOM ANCHORS. BUT, |
| | INSTALLATION SCHEDULE WAS NEVER REVISED |
| | TO REFLECT THIS CHANGE. REVISE AS |
| | REQUIRED. |
| | |
| | 3- FOLDING SHUTTER CORPORATION COVER |
| | PAGE INDICATES THAT PRODUCT APPROVAL |
| | COMPLIANCE REPORT IS AN SBCCI REPORT. |
| | REPORT SUBMITTED IS A DADE COUNTY NOA |
| | (WHICH, CORRESPONDS TO THE REPORT THAT |
| | WAS SUBMITTED FOR FLORIDA PRODUCT |
| | APPROVAL). REVISE COVER PAGE TO REFLECT |
| | THE DADE COUNTY NOA NOT THE SBCCI. |
| | NOTE: DADE COUNTY NOA'S AND SBCCI |
| | REPORTS ARE TWO DIFFERENT REPORTS. WE |
| | ONLY NEED THE ONE THAT WAS SUBMITTED FOR |
| | FLORIDA PRODUCT APPROVAL. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT (561)805-6712. |
| | |