| 2005-08-09 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED FLORIDA PRODUCT APPROVAL OR |
| | APPLY FOR LOCAL PRODUCT APPROVAL AS |
| | REQUIRED BY RULE 9B-72 FROM DCA. SEE |
| | WWW.FLORIDABUILDING.ORG FOR MORE |
| | INFORMATION REGARDING THE MANDATORY |
| | PRODUCT APPROVALS. ACCORDING TO THE |
| | BUILDING OFFICIAL DADE COUNTY NOA ALONE |
| | IS NOT AN STATEWIDE FLORIDA PRODUCT |
| | APPROVAL. MANUFACTURER MAY APPLY FOR |
| | LOCAL PRODUCT APPROVAL USING THE DADE |
| | COUNTY NOA BY COMPLETING THE LOCAL |
| | PRODUCT APPROVAL FORM DOWNLOADED FROM |
| | WWW.FLORIDABUILDING.ORG. |
| | |
| | 2- ACCORDING TO ANCHOR CHART #7 ON SHEET |
| | 5 OF 5: A) SOME ANCHORS NEED TO BE |
| | SPACED AT 18"O.C. NOT 24"O.C. (SEE |
| | OPEN'G 7 & 8). |
| | B) CLARIFY WHY OPENINGS 2 AND 3 HAVE 24" |
| | SPACING ON TOP AND 21" SPACING AT |
| | BOTTOM. ACCORDING TO CHART #7 BOTH SHALL |
| | BE SPACED AT 21" O.C. |
| | |
| | 3- NOTICE OF COMMENCEMENT IS EXPIRED |
| | AFTER 90 DAYS OF RECORDING AND NO WORK |
| | IS STARTED. NEED RE-RECORDED N.O.C. |
| | |
| | 4- FOLDING SHUTTER CORPORATION COVER |
| | PAGE INDICATES THAT PRODUCT COMPLIANCE |
| | REPORT IS AN SBCCI REPORT. REPORT |
| | SUBMITTED IS A DADE COUNTY NOA. REVISE |
| | AS REQUIRED TO MATCH INFORMATION |
| | REQUESTED ON ITEM #1 ABOVE. |
| | |