| Plan Review Notes For Permit 05080028 |
| Permit Number |
05080028 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-11 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SHOW FOOTER STEEL AS PART OF | | | THE GEC SINCE IT WILL BE AVAILABLE PER | | | 250.50. ALSO SEE 230.70 CWPB AMMENDMENTS | | | FOR DISCONNECT REQUIREMENT. | | | | | | 2} LIST THE BATH GFI AS REQUIRED BY | | | 210.11(C)(3), ON THE PANEL SCHEDULE. | | | | | | 3} THE PERSON RESPONSIBLE FOR THE DESIGN | | | SHALL PPRINT AND SIGN NAME ON SAME PER | | | 104.2.1 FBC. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|