Plan Review Notes
Plan Review Notes For Permit 05071340
Permit Number 05071340
Review Stop E
Sequence Number 2
Notes
Date Text
2006-02-17 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE COMPLETE THE LOAD
 CALCULATIONS. SHOW TOTALS AND INDICATE
 CALCULATION USED. EG: 220.30,220.31.
  
 2} PLEASE INDICATE ROOM DESIGNATION ON
 THE PLANS.
  
 3} PLEASE SHOW ( AND DESIGNATE) ALL
 ELECTRICAL SERVICE EQUIPMENT ON THE
 PLAN.
  
 4} THE PANEL SHOWN INSIDE THE HOUSE IN
 WHAT APPEARS TO BE A CLOSET MUST COMPLY
 WITH 240.24, MAY HAVE TO BE MOVED OR
 MADE TO COMPLY. PLEASEV SEE ARTICLE.
  
 5} PLEASE SEE THAT SMOKE DETECTORS ARE
 REQUIRED BY NFPA-72 8-1.4.2 AND FBC
 905.2.5.
  
 6} RECEPTALE SPACING MUST COMPLY WITH
 210.52(A) & (B). SEE REVIEWED PLAN FOR
 SOME AREAS MISSED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved