| Plan Review Notes For Permit 05071340 |
| Permit Number |
05071340 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-02-17 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE COMPLETE THE LOAD | | | CALCULATIONS. SHOW TOTALS AND INDICATE | | | CALCULATION USED. EG: 220.30,220.31. | | | | | | 2} PLEASE INDICATE ROOM DESIGNATION ON | | | THE PLANS. | | | | | | 3} PLEASE SHOW ( AND DESIGNATE) ALL | | | ELECTRICAL SERVICE EQUIPMENT ON THE | | | PLAN. | | | | | | 4} THE PANEL SHOWN INSIDE THE HOUSE IN | | | WHAT APPEARS TO BE A CLOSET MUST COMPLY | | | WITH 240.24, MAY HAVE TO BE MOVED OR | | | MADE TO COMPLY. PLEASEV SEE ARTICLE. | | | | | | 5} PLEASE SEE THAT SMOKE DETECTORS ARE | | | REQUIRED BY NFPA-72 8-1.4.2 AND FBC | | | 905.2.5. | | | | | | 6} RECEPTALE SPACING MUST COMPLY WITH | | | 210.52(A) & (B). SEE REVIEWED PLAN FOR | | | SOME AREAS MISSED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | |
|