| Plan Review Notes For Permit 05071340 |
| Permit Number |
05071340 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-15 00:00:00 | DENIED: | | | 1.PLAN SHEET MP-1, MISSING DUCT SIZES | | | FOR THE BRANCH DUCTS AND ALSO ONE GRILLE | | | SIZE. | | | | | | 2.PLAN SHEET MP-1, MECHANICAL NOTE | | | INDICATES 4" SLAB FOR THE CONDENSER. | | | PER 2001 FBC(M)304.7, SLAB SHALL EXTEND | | | A MINIMUM OF 2" ABOVE THE ADJOINING | | | GRADE. | | | | | | 3.AUXILIARY DRAIN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 | | | FBC(M)307.2.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|