| Plan Review Notes For Permit 05071304 |
| Permit Number |
05071304 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-01 00:00:00 | ******** UNSAT ******** | | | | | | 1)NOTE: PLEASE SEE THE MISSING REQUIRED | | | "PRINTED NAME AND LICENSE NUMBER " FOR | | | THE ARCHITECT OF RECORD ON PLANS. | | | FAC 61G1-16.004 | | | | | | 2)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH THE SUBMITTED | | | PANEL SCHEDULE. | | | PLEASE SEE "NOTES" TO POWER PLANS | | | MENTIONS, "R" INDICATES RELOCATED | | | OUTLETS TO EXSITING CIRCUITS? PLEASE SEE | | | AN "R" COULD NOT BE LCOATED IF INDEED | | | RECEPTS ARE EXSITNG. | | | | | | 3)NOTE: PLEASE VERIFY BY NOTE IF TENANT | | | OCCUPANTS HAVE ACCESS TO OVER CURRENT | | | PROTECTIVE DEVICES FOR THEIR SPACE. | | | IS BLDG UNDER 24 HR MANG? | | | PLEASE SEE NEC 240.24 | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER TRADES WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELETCRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|