| Plan Review Notes For Permit 05071284 |
| Permit Number |
05071284 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-11 00:00:00 | DENIED:REVIEWED UNDER THE 2004 FBC | | | NO MECHANICAL PLANS SUBMITTED OR | | | ANALYSIS SUBMITTED FOR REVIEW.PLEASE | | | PROVIDE THE FOLLOWING INFORMATION. | | | | | | 1.PLEASE INDICATE EXISTING HVAC & | | | EXHAUST SYSTEMS IN ACCORDANCE WITH 2004 | | | FBC(M)401.3.PLEASE NOTE, CORRIDORS | | | SHALL NOT BE USED AS RETURN AIR PLENUMS | | | PER 2004 FBC 423.15.2. | | | | | | 2.PROVIDE EQUIPMENT SCHEDULE (NEW OR | | | EXISTING). | | | | | | 3.INDICATE ANY NEW WORK OR | | | MODIFICATION TO DUCT & GRILLE LAYOUT. | | | | | | 4.PLANS DO NOT INDICATE FIRE RATING OF | | | WALLS, PARTITIONS OR SEPARATION | | | REQUIREMENTS.PLEASE PROVIDE DETAILS | | | FOR PENETRATIONS. | | | | | | 5.PROVIDE OUTSIDE AIR CALCULATIONS PER | | | 2004 FBC(M) TABLE 403.3. | | | | | | 6.BATHROOM EXHAUST SHALL BE A MINIMUM | | | OF 50 CFM PER WATER CLOSET OR URINAL. | | | BATHROOMS SHALL BE CONTINUOUSLY | | | VENTILATED DURING BUILDING OCCUPANCY OR | | | COMPLY WITH EXCEPTION UNDER 2004 FBC | | | 423.15.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|