| Plan Review Notes For Permit 05071282 |
| Permit Number |
05071282 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-28 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | MYRON JACOBS(561) 805 6726 | | | E-MAIL: [email protected] | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | F.S.= FLORIDA (STATE) STATUTE | | | | | | 1) FBC 1606.2.5THE SYSTEM SELECTED | | | FROM THE SUBMITTED FLAT ROOF PRODUCT | | | APPROVAL NOA HAS A MAXIMUM DESIGN | | | PRESSURE OF LESS THAN -89 PSF AND CITES | | | GENERAL LIMITATION #9 (SEE PAGE 33 OF | | | 38).GENERAL LIMITATION #9 PROHIBITS | | | RATIONAL ANALYSIS OR EXTRAPOLATION TO | | | ENHANCE THE UPLIFT PRESSURE AT PERIMETER | | | AND CORNER AREAS BY REDUCING THE | | | FASTENER SPACING IN THESE AREAS.EITHER | | | SELECT AN ALTERNATIVE SYSTEM (OR PRODUCT | | | APPROVAL) THAT DOES NOT CITE GENERAL | | | LIMITATION #9.ALTERNATIVELY IF THE | | | SELECTED SYSTEM DOES CITE GENERAL | | | LIMITATION #9, IT MUST HAVE A MAXIMUM | | | DESIGN PRESSURE THAT EXCEEDS THE | | | PRESSURE IN ROOF ZONE 3 (TYPICALLY -89 | | | PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR | | | LESS). | | | | | | BUILDING PLAN REVIEW | | | MYRON JACOBS | | | TEL: (561)805-6726 | | | FAX: (561)659-8026 | | | [email protected] | | | |
|