| 2005-08-16 00:00:00 | *** UNSAT *** |
| | |
| | 1)NOTE: PLEASE SEE NEW RISER DIAGRAM |
| | SUBMITTED. |
| | PLEASE SEE MISSING GROUNDING ELECTRODE |
| | SYSTEM. PLEASE SEE 250.50,250.66,250.24 |
| | ETC. |
| | PLEASE SEE A MIN OF TWO GROUND RODS WILL |
| | BE REQUIRED. |
| | PLEASE SEE MAIN SHOWN AT FPL STRUCTURE |
| | AND THEN OVER TO A METER AND THEN NEW |
| | MPC. |
| | PLEASE CLARIFY MAIN DISCONNECTLOCATED ON |
| | THE "LINE SIDE" OF THE FPL METERING |
| | DEVICE? |
| | PLEASE SEE MISSING EQUIPMENT GROUNDING |
| | CONDUCOTR AFTER THE FIRST MEANS OF |
| | DISCONNECT. 250.122,250.110,250.24 |
| | |
| | 2)NOTE: PLEASE SEE RISER INDICATES NO |
| | MORE THAN 10' FOR A "TAP"? |
| | PLEASE SEE INSTALLATION AS SHOWN WILL |
| | EXCEED 10'. |
| | PLEASE ALSO SEE ANY TAPS MUST TERMINATE |
| | IN OCP. THIS CAN NOT GO TO A METER. |
| | 240.21,240.4,310.16 ETC |
| | |
| | 3)NOTE: PLEASE SEE MPC MUST ALSO |
| | INDICATE THE MCB AS NOTED ON RISER. |
| | PLEASE SUBMIT THE MANUFACTURE/SPEC CUT |
| | SHEETS FOR THIS MPC PANEL. |
| | PLEASE BE SURE LISITNG PER A NRTL. |
| | |
| | 4)NOTE: PLEASE SEE ONLY ONE COPY OF |
| | PLANS WERE SUBMITTED. PLEASE SUBMIT TWO |
| | SIGNED, DATED AND SEALED COPIES. |
| | PLEASE ALSO SEE PLANS MUST BE "SIGNED" |
| | BY THE ENGINEEROF RECORD WITH SIGNATURE |
| | AS IS ON FILE. |
| | FS 471.025 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |