2005-08-16 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE NEW RISER DIAGRAM
 SUBMITTED.
 PLEASE SEE MISSING GROUNDING ELECTRODE
 SYSTEM. PLEASE SEE 250.50,250.66,250.24
 ETC.
 PLEASE SEE A MIN OF TWO GROUND RODS WILL
 BE REQUIRED.
 PLEASE SEE MAIN SHOWN AT FPL STRUCTURE
 AND THEN OVER TO A METER AND THEN NEW
 MPC.
 PLEASE CLARIFY MAIN DISCONNECTLOCATED ON
 THE "LINE SIDE" OF THE FPL METERING
 DEVICE?
 PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCOTR AFTER THE FIRST MEANS OF
 DISCONNECT. 250.122,250.110,250.24
  
 2)NOTE: PLEASE SEE RISER INDICATES NO
 MORE THAN 10' FOR A "TAP"?
 PLEASE SEE INSTALLATION AS SHOWN WILL
 EXCEED 10'.
 PLEASE ALSO SEE ANY TAPS MUST TERMINATE
 IN OCP. THIS CAN NOT GO TO A METER.
 240.21,240.4,310.16 ETC
  
 3)NOTE: PLEASE SEE MPC MUST ALSO
 INDICATE THE MCB AS NOTED ON RISER.
 PLEASE SUBMIT THE MANUFACTURE/SPEC CUT
 SHEETS FOR THIS MPC PANEL.
 PLEASE BE SURE LISITNG PER A NRTL.
  
 4)NOTE: PLEASE SEE ONLY ONE COPY OF
 PLANS WERE SUBMITTED. PLEASE SUBMIT TWO
 SIGNED, DATED AND SEALED COPIES.
 PLEASE ALSO SEE PLANS MUST BE "SIGNED"
 BY THE ENGINEEROF RECORD WITH SIGNATURE
 AS IS ON FILE.
 FS 471.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717