| Plan Review Notes For Permit 05071270 |
| Permit Number |
05071270 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-29 00:00:00 | ********* UNSAT ********** | | | | | | 1)NOTE: PLEASE REVISE RISER DIAGRAM | | | WHICH SHOWS SERVICE FROM FPL COMING | | | DIRECTLY INTO ATS? | | | 215.5 | | | | | | 2)NOTE: PLEASE INDICATE IF MAIN IS IN | | | CLOSE PROXIMITY TO SERVICE ATS. | | | THE MAIN MAY BE DIRECTLY BEHINED OR | | | AJACENT TO ATS. | | | 230.72,240.4 ETC. | | | | | | 3)NOTE: PLEASE SEE 250.66 FOR GROUNDING | | | ELECTRODE SYSTEM. PLEASE SEE #6 SHOWN IS | | | NOT LARGE ENOUGH. | | | | | | 4)NOTE: PLEASE PROVIDE MANUFACTURE | | | SHEETS FOR ATS. THESE SHOULD INDICATE | | | EQUIPMENT BEING SERVICE ENTRANCE RATED. | | | 215.5 | | | | | | 5)NOTE: PLEASE INCLUDE COLD WATER PIPE | | | AS PART OF THE GROUNDING ELECTRODE | | | SYSTEM. | | | 250.50 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|