Date Text
2005-08-09 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
  
 1} THE PERSON RESPONSIBLE FOR THE
 DRAWING MUST PRINT AND SIGN NAME TO
 SAME, 104.2.1 FBC.
  
 2} PLEASE SUBMIT A SITE PLAN INDICATING
 THE PHYSICAL LOCATION OF THESERVICE
 EQUIPMENT AND THE EMERGENCY EQUIPMENT SO
 THAT COMPLIANCE WITH 225.31 THROUGH
 225.37 CAN BE DETERMINED.
  
 3} INDICATE WHICH OF THE TRANSFER
 SWITCHES IS PROPOSED. PLEASE SEE IT MUST
 BE SERVICE RATED PER 225.36 AND 225.31.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  