| Plan Review Notes For Permit 05071269 |
| Permit Number |
05071269 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-09 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | | | | 1} THE PERSON RESPONSIBLE FOR THE | | | DRAWING MUST PRINT AND SIGN NAME TO | | | SAME, 104.2.1 FBC. | | | | | | 2} PLEASE SUBMIT A SITE PLAN INDICATING | | | THE PHYSICAL LOCATION OF THESERVICE | | | EQUIPMENT AND THE EMERGENCY EQUIPMENT SO | | | THAT COMPLIANCE WITH 225.31 THROUGH | | | 225.37 CAN BE DETERMINED. | | | | | | 3} INDICATE WHICH OF THE TRANSFER | | | SWITCHES IS PROPOSED. PLEASE SEE IT MUST | | | BE SERVICE RATED PER 225.36 AND 225.31. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|