2006-01-17 00:00:00DENIED 4TH TIME
  
 REFERENCE: FBC-2001 FUEL GAS. CITY OF
 WEST PALM BEACH AMENDMENTS TO FBC,
 CHAPTER 1.
  
 THE FOLLOWING INFORMATION IS STILL
 NEEDED FOR GAS PERMIT:
 1. SEC 104.2 DRAWINGS AND SPECIFICATIONS
 104.2.4 REQUIREMENTS: DRAWINGS DRAWN TO
 SCALE WITH SUFFICENT CLARITY AND DETAIL
 TO INDICATE THE NATURE AND CHARACTER OF
 THE WORK.
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.THIS DRAWING SHALL SHOW
 EXISTING SYSTEM TO HOUSE WITH BTU LOAD
 CAPACITIES TO THE APPLIANCES AND THE
 LONGEST LENGTH FROM METER.ALSO THE REGU-
 LATER SUBMITTED MUST BE CLEARLY
 INDICATED ON DRAWING.
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2. NEED
 MANUFACTURE CUT OF GENERATOR.
  
 END OF COMMENTS:
  