Plan Review Notes
Plan Review Notes For Permit 05071268
Permit Number 05071268
Review Stop G
Sequence Number 3
Notes
Date Text
2005-12-10 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
 DENIED 3RD TIME
 1.PLEASE "READ" AND ADDRESS PREVIOUS
 COMMENTS ATTACHED.
  
 2.GAS TABLE SUBMITTED IS NOT ADOPTED BY
 THE CITY OF WEST PALM BEACH
 USE FBC 2001 FUEL GAS TAB 402.(2)
  
 3.SEC 104.2.1 DRAWINGS & SPECIFICATIONS.
 DRAWINGS DRAWIN TO SCALE WITH SUFFICENT
 CLARITY AND DETAIL TO INDICATE THE
 NATURE AND CHARACTER OF THE WORK.
  
 4. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS
 FBC-2001 FUEL GAS CODE SEC 402.2
  
 6. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM.
  
 7. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
  
 8. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 END OF COMMENTS, QUESTIONS 561-805-6692