| 2005-12-10 00:00:00 | PAUL SCHMITZ |
| | FBC2001 FUEL GAS CODEPLAN REVIEW |
| | FBC 2001 PLUMBING CODEPLAN REVIEW |
| | FBC 2001 FL ACESSIBILITY CODE PLAN |
| | REVIEW |
| | DENIED 3RD TIME |
| | 1.PLEASE "READ" AND ADDRESS PREVIOUS |
| | COMMENTS ATTACHED. |
| | |
| | 2.GAS TABLE SUBMITTED IS NOT ADOPTED BY |
| | THE CITY OF WEST PALM BEACH |
| | USE FBC 2001 FUEL GAS TAB 402.(2) |
| | |
| | 3.SEC 104.2.1 DRAWINGS & SPECIFICATIONS. |
| | DRAWINGS DRAWIN TO SCALE WITH SUFFICENT |
| | CLARITY AND DETAIL TO INDICATE THE |
| | NATURE AND CHARACTER OF THE WORK. |
| | |
| | 4. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | |
| | 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | |
| | 6. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. |
| | |
| | 7. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | |
| | 8. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | END OF COMMENTS, QUESTIONS 561-805-6692 |