| Plan Review Notes For Permit 05071268 |
| Permit Number |
05071268 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-09 00:00:00 | DENIED; | | | 1.TOTAL LOAD OF GAS APPLIANCES SHALL BE | | | CALCULATED WHEN ADDING AN ADDITIONAL GAS | | | APPIANCE. | | | 2.LONGEST RUN WOULD INCLUDE THE PIPING | | | INSIDE THE HOUSE. | | | 3.IS PIPE TO GENERATOR STRAPED TO WALL, | | | BURIED OR JUST HANG WITH NO SUPPORT? | | | 4.SUBIT A CUT SHEET FOR THE GENERATOR | | | THAT SHOWS BTU'S REQUIRED. | | | 5.THE PERSON WHO DREW THE PLAN SHALL | | | PRINT AND SIGN HIS OR HER NAME TO THE | | | DRAWING. | | | 6.SHOW TEE REQUIRED FROM METER TO GEN. | | | TO HOUSE PIPING. | | | GAS PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|