Plan Review Notes
Plan Review Notes For Permit 05071231
Permit Number 05071231
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-29 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTORS SHALL NOT BE INSTALLED UNTIL
 AFTER THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE 250.6,250.24.
 PLEASE SEE # 6'S FROM METER TO ALL
 MAINS.
  
  
 2)NOTE: PLEASE SEE LISTED NOTE MENTIONS
 TO USE A LISTED CABLE FOR TRAILERS? IF
 USING A CABLE INSTEAD OF THE CONDUIT AND
 CONDUCTORS BURIED AT 24", PLEASE SPECIFY
 TYPE OF CABLE TO BE USED.
 PLEASE SEE ANY REQUIREMENTS FROM 545 FOR
 PROTECTION OF CONDUCTORS.
  
 3)NOTE: PLEASE SEE A MIN OF 2 GRND RODS
 ARE REQUIRED.250.50
 PLEASE ALSO SEE A GRND ROD WILL ALSO BE
 REQUIRED AT TRAILER.545.12
  
 4)NOTE: PLEASE SEE PLANS ARE REQUIRED TO
 HAVE THE PRINTED NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR PLANS PER FBC
 104.2.1 AND ARE NOT REQUIRED TO BE
 NOTORIZED, HOWEVER IF NOTORIZED; THEN
 NOTORY MUST PROPERLY NOTORIZE DOCUMENT
 UNDER FS 117.
  
 5)NOTE: PLEASE SEE VALUATION FOR PERMIT
 APPLICATION MUST BE BASED ON ALL LABOR
 PLUS MATERIALS, EVEN IF ANY MATERIALS
 ARE OWNER SUPPLIED.
 PLEASE SEE FBC 104.6.5
  
 6)NOTE: PLEASE CORRELATE RISER DIAGRAM
 WITH PANEL/DISC DETAIL ON 2ND PAGE,
 PLEASE SEE RISER SHOWS MAIN #4 AS 100A,
 HOWEVER DETAIL SHOWS 200A?
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW