| 2005-07-29 00:00:00 | ********** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SEE EQUIPMENT GROUNDING |
| | CONDUCTORS SHALL NOT BE INSTALLED UNTIL |
| | AFTER THE FIRST MEANS OF DISCONNECT. |
| | PLEASE SEE 250.6,250.24. |
| | PLEASE SEE # 6'S FROM METER TO ALL |
| | MAINS. |
| | |
| | |
| | 2)NOTE: PLEASE SEE LISTED NOTE MENTIONS |
| | TO USE A LISTED CABLE FOR TRAILERS? IF |
| | USING A CABLE INSTEAD OF THE CONDUIT AND |
| | CONDUCTORS BURIED AT 24", PLEASE SPECIFY |
| | TYPE OF CABLE TO BE USED. |
| | PLEASE SEE ANY REQUIREMENTS FROM 545 FOR |
| | PROTECTION OF CONDUCTORS. |
| | |
| | 3)NOTE: PLEASE SEE A MIN OF 2 GRND RODS |
| | ARE REQUIRED.250.50 |
| | PLEASE ALSO SEE A GRND ROD WILL ALSO BE |
| | REQUIRED AT TRAILER.545.12 |
| | |
| | 4)NOTE: PLEASE SEE PLANS ARE REQUIRED TO |
| | HAVE THE PRINTED NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR PLANS PER FBC |
| | 104.2.1 AND ARE NOT REQUIRED TO BE |
| | NOTORIZED, HOWEVER IF NOTORIZED; THEN |
| | NOTORY MUST PROPERLY NOTORIZE DOCUMENT |
| | UNDER FS 117. |
| | |
| | 5)NOTE: PLEASE SEE VALUATION FOR PERMIT |
| | APPLICATION MUST BE BASED ON ALL LABOR |
| | PLUS MATERIALS, EVEN IF ANY MATERIALS |
| | ARE OWNER SUPPLIED. |
| | PLEASE SEE FBC 104.6.5 |
| | |
| | 6)NOTE: PLEASE CORRELATE RISER DIAGRAM |
| | WITH PANEL/DISC DETAIL ON 2ND PAGE, |
| | PLEASE SEE RISER SHOWS MAIN #4 AS 100A, |
| | HOWEVER DETAIL SHOWS 200A? |
| | 215.5 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |