| 2005-07-30 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: |
| | ADD: |
| | CONT: |
| | TEL: (561)###-#### |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2A) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 2B)FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) SLIDING DOORS - REPORT SUBMITTED |
| | MISSING FL COVERSHEET |
| | B) HORIZONTAL SLIDING WINDOWS NO REPORT |
| | |
| | NOR STATE FL NUMBER SUBMITTED. |
| | C) EFIS SYSTEMS- STO MISSING REPORT AND |
| | FL COVER SHEET. |
| | D) PLANS DO NOT INDICATE LOUVERS, IF |
| | THE HAS LOUVERS REPORTS ARE |
| | REQUIRED. |
| | NOTE, MOST EFIS REPORTS INDICATE THAT |
| | THIS SYSTEM IS NOT TO BE USED ON |
| | HORIZONTAL SURFACES. |
| | |
| | 3) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, PLANS |
| | DO NOT INDICATE IF NEGATIVE PRESSURES |
| | TAKEN ARE END ZONE PRESSUES AND WHAT |
| | TRIUTARY AREA (WINDOWS AND DOORS) WORST |
| | CASE 20 SQ FT. |
| | |
| | 4) ENGINEERING SHEETS 007 AND 010 BOTH |
| | INDICATE A 2X WOOD BUCK BUT NO |
| | INFORMATION IS PROVIDED FOR THE |
| | ATTACHMENT OF BUCK TO STRUCTURE? |
| | 1606.4.4 ANCHOR METHODS. PROVIDE |
| | INFORMATION FOR INSTALLATION OF DOOR |
| | AND WINDOW BUCKS. |
| | |
| | 5) STO DETAIL SHEET INDICATES A |
| | SUPPORTING SUBSTRATE OR SUBSHEATHING, |
| | PLANS DO NOT PROVIDE WHAT THIS WILL BE, |
| | PLEASE IDENTIFY , SECTION 604 TYPE II |
| | CONSTRUCTION. |
| | TYPE II CONSTRUCTION |
| | TYPE II IS CONSTRUCTION IN WHICH THE |
| | STRUCTURAL MEMBERS INCLUDING EXTERIOR |
| | WALLS, INTERIOR BEARI5) STO DETAIL SHEET |
| | INDICATES A |
| | SUPPORTING SUBSTRATE OR SUBSHEATHING, |
| | PLANS DO NOT PROVIDE WHAT THIS WILL BE, |
| | PLEASE IDENTIFY.SECTION 604NG WALLS, |
| | COLUMNS, |
| | BEAMS, GIRDERS, TRUSSES, ARCHES, |
| | FLOORS AND ROOFS ARE OF NONCOMBUSTIBLE |
| | MATERIALS AND ARE PROTECTED SO AS TO |
| | HAVE FIRE RESISTANCE NOT LESS THAN THAT |
| | SPECIFIED FOR THE STRUCTURAL |
| | ELEMENTS AS SPECIFIED IN TABLE 600. |
| | **** CHECK NOA TESTING TO SEE WHAT |
| | SUBSTRATE WAS USED TO ACHIEVE PRESSURES |
| | OF NOA! |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |