| Plan Review Notes For Permit 05071213 |
| Permit Number |
05071213 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-08-09 00:00:00 | ********** UNSAT ************ | | | | | | PLEASE SEE NOTES FROM FIRST REVIEW ALSO. | | | | | | | | | 1)NOTE: PLEASE SEE A MEANS OF DISCONNECT | | | ALONG WITH OVERCURRENT PROTECTION IS | | | REQUIRED ON THE "OUTSIDE" OF BLDG. | | | PLEASE SEE 230.70,230.6. | | | | | | 2)NOTE: PLEASE SHOW ANY FPL METERING | | | DEVICES. | | | PLEASE SEE MIN GROUNDING ELECTRODE | | | SYSTEM SHALL BE SHOWN ON RISER AT | | | SERVICE LOCATION. | | | PLEASE SEE ANY EQUIPMENT GORUNDING | | | CONDUCTORS FROM MAIN TO SUB PANEL SHALL | | | BE SIZED PER 250.122 | | | | | | 3)NOTE: PLEASE SEE FEEDER SIZE HAS | | | DECREASED TO 500MCM. IS THIS COPPER | | | (CU)? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|