| Plan Review Notes For Permit 05071213 |
| Permit Number |
05071213 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-29 00:00:00 | ********** UNSAT ********** | | | | | | 1)NOTE: PLEASE SEE 240.6, 310.16 600MCM | | | ALUM IS NOT RATED FOR 400A'S. | | | MAX 350A'S. | | | | | | 2)NOTE: PLEASE SEE NO MORE THAN 8' OF | | | UNPROTECTED CONDUCTOR ARE PERMITTED | | | INSIDE BLDG WITH OUT OCP . 230.70 | | | PLEASE ALSO SEE NO MAIN SHOWN. 230.70 | | | | | | 3)NOTE: PLEASE SEE 250.6, AN EQUIPMENT | | | GROUNDING CONDUCTOR IS ONLY INSTALLED | | | AFTER THE FIRST MEANS OF DISCONNECT. | | | 250.24. | | | | | | PLEASE REVISE AND SUBMIT THE ABOVE | | | INFORMATION FOR REVIEW. IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|