| Notes |
| Date |
Text |
| 2007-03-07 15:38:09 | REDLINED PLANS. | | | | | | NO MORE THAN 8FT OF UNPROTECTED CONDUCTORS IN TOTAL | | | LENGTH INSIDE DWELLING. 230.70 90.4. | | | THIS WILL BE VIF, AND MAIN W/ OVER CURRENT PROTECTION | | | MAY BE REQUIRED OUTSIDE DWELLING AS STATED ON PLANS. | | | AT OWN RISK TO CONTRACTOR AS RISER WAS CHANGED FROM | | | ORIGINAL PLANS. |
|