| Plan Review Notes For Permit 05071205 |
| Permit Number |
05071205 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2007-03-02 13:17:13 | | | | * UNSAT * | | | | | | * PLEASE KNOW AS THE RISER CHANGED FROM THE ORIGINALLY | | | PERMITTED PLANS THERE IS STILLS QUESTIONS AS STATED. | | | | | | | | | 1) NOTE: PLEASE SEE RISER NOW SHOWS A NEW GUTTER WHICH | | | FEEDS TWO MBC PANELS.PLEASE SEE 230.70 AS NO MORE | | | THAN 8FT OF UNPROTECTED CONDUCTORS ARE PERMITTED INSIDE | | | THE BUILDING. THE CODE ACTUALLY DOES NOT STATE THE | | | LENGHT PERMITTED AS SOME AHJ'S REQUIRE "0" FT AND | | | OTHERS ALLOW MORE. IN TEH CITY OF WEST PALM BEACH AND | | | PALM BEACH COUNTY THE OLD LOCAL AMENDMENTS LIMITED THE | | | LENGTHS TO 8FEET AND WE AS TEH AHJ HAS RETAINED THIS | | | LMIT. | | | PLEASE KNOW THAT THIS IS BASED ON THE TOTAL LENGTH AND | | | IF THERE IS MORE THAN 8FT THEN, MAIN(S) WITH OVER | | | CURRENT PROTECTION WOULD BE REQUIRED OUTSIDE. | | | PLEASE ALSO SEE THAT EQUIPMENT GROUNDING WOULD THEN BE | | | REQUIRED FROM MAINS TO ANY SUB PANELS. | | | PLEASE SEE RISER AS SHOWN WOULD REQUIRE MAIN | | | DISCONNECTS W/ OVER CURRENT PROTECTION OUTSIDE. | | | 250.6, 250.24, 250.122 | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|