Plan Review Notes
Plan Review Notes For Permit 05071205
Permit Number 05071205
Review Stop E
Sequence Number 4
Notes
Date Text
2007-02-02 17:25:58 
  
 *** UNSAT ***
  
 ** PLEASE SEE RISER HAS COMPLETELY BEEN REVISED AND THE
 FOLLOWING COMMENTS APPLY.
  
 1) NOTE: PLEASE SEE RISER NOW SHOWS A NEW GUTTER WHICH
 FEEDS TWO MBC PANELS. PLEASE SEE PLANS DO NOT INDICATE
 THE LOCATION OF THE NEW GUTTER. PLEASE SEE 230.70 AS NO
 MORE THAN 8FT OF UNPROTECTED CONDUCTORS ARE PERMITTED
 INSIDE THE BUILDING.
 PLEASE SEE RISER AS SHOWN WOULD REQUIRE MAIN
 DISCONNECTS W/ OVER CURRENT PROTECTION OUTSIDE.
  
 2) NOTE: PLEASE SEE PREVIOUS PLANS ISSUED FOR PERMIT
 WERE REDLINED AS CONDUITS FROM THE METER TO THE FIRST
 MEANS OF DISCONNECT SHALL CONTAIN ANY *EQUIPMENT
 GROUNDING CONDUCTORS*. PLEASE SEE THE PANEL SCHEDULES
 INDICATE EQUIPMENT GROUNDS AND THE RISER NOTES ALSO
 INDICATE EQUIPMENT GROUNDS.
 PLEASE SEE 250.6, 250.24B.
  
 3) NOTE:PLEASE SEE THE SIZE OF THE GROUNDING
 ELECTRODE CONDUCTOR HAS DECREASED AND IS REQUIRED TO BE
 SIZED PER 250.66 (MIN #2) BASED ON THE SERVICE AS
 SHOWN.
 310.16
  
 4) NOTE: PLEASE SEE 210.4B, IF THE DISHWASHER AND
 DISPOSAL FEED TO THE SAME DEVICE, THEN THIS WOULD
 REQUIRE A 2-POLE BREAKER FOR EACH OF THESE. PLANS ONLY
 SEEM TO SHOW DEVICE. PLEASE VERIFY THIS AND ADJUST THE
 BRANCH BREAKER AS NEEDED.
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE PANEL SCHEDULE INDICATES THE POOL
 PUMP BEING ON A SINGLE POLE 20AMP CIRCUIT, YET THE LOAD
 CALCULATIONS INDICATE A LOAD OF 2530VA WHICH EXCEEDS
 THE RATING OF THIS.
 PLEASE ALSO SEE THE POOL LIGHTS CIRCUIT IS SHOWING
 2000VA YET ALSO ONLY ON A SP 20A CIRCUIT.
 PLEASE VERIFY THIS.
 240.4, 310.16, 230.42 ETC
  
 6) NOTE: PLEASE SEE THE PANEL SCHEDULE SHOULD BE DIRECT
 FOR ALL CIRCUITS. PLEASE SEE 408.4.
 *REQUIRES THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.*
 THIS IS IN ORDER TO VERIFY MANY ITEMS PER 240.4 AND
 310.16.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]