2007-01-12 10:57:58MECHANICAL REVISION
 *** DENIED ***
 1) NEED TO SHOW SIZE OF SUPPLY AIR TRUNK LINE LEAVING
 AHU #2.
  
 2) NEED TO SHOW SIZE OF BOTH RETURN AIR GRILLS TO AHU
 #2.
  
 3) PLEASE SHOW HOW MANY SUPPLY AIR DUCTS ARE GOING TO
 THE FIRST FLOOR FROM AHU #1.
  
 4) PLEASE SHOW WERE THE CLOTHES DRYER VENT IS TO
 TERMINATE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.