| 2006-01-09 00:00:00 | ************ UNSAT********** |
| | |
| | ** PLEASE SEE NOTES BELOW ALSO FROM |
| | PREVIOUS REVIEW. |
| | |
| | 1)NOTE: PLEASE SEE MISSING SMOKE |
| | DETECTOR TO BE LOCATED ON 2ND FLR |
| | OUTSIDE BEDRMS MAST, BEDRM #3. |
| | NFPA-72 11.5.1.1 |
| | PREVIOUS REVIEW. |
| | |
| | 2)NOTE: PLEASE SEE AHU'S LOCATED ON 2ND |
| | FLR WHICH DO NOT SHOW ANY ACCESS, OR |
| | MEANS OF DISCONNECT REQUIRED. |
| | PLEASE SHOW.215.5,440 |
| | LTS, RECEPTS. 210.70,210.63 UNABLE TO |
| | VERIFY, DUE TO PLANS NOT INDICATING THE |
| | ACCESS. ARE THESE LOCATED IN ATTIC? |
| | PLEASE SEE CU'S ARE NOW BEING SHOWN, |
| | HOWEVER DISCONNECT'S ARE BEING SHOWN |
| | BEHIND UNITS AND NOT MEETING 110.26. |
| | PREVIOUS REVIEW. |
| | |
| | 3)NOTE: PLEASE SEE PLANS ARE MISSING |
| | SERVICE. PLEASE SEE ONE PANEL IS LOCATED |
| | ON FIRST FLR OUTSIDE LAUNDRY RM. |
| | PLEASE SEE PREVIOUS REVIEW. |
| | SHOW ALL EQUIPMENT AND LOCATION. |
| | 215.5,240.24 ETC |
| | |
| | 4)NOTE: PLEASE SEE RISER NOW INDICATE AN |
| | "EQUIPMENT GROUNDING CONDUCTOR" FROM |
| | METER TO THE MCB PANEL "A". PLEASE SEE |
| | 250.6, 250.24 WHIC DOES NOT PERMIT AN |
| | "EQUIPMENT GROUNDING CONDUCTOR" FROM THE |
| | METER TO THE FIRST MEANS OF DISCONNECT. |
| | THE ONLY CONDUCTORS SHOULD BE THE "HOT" |
| | PHASE CONDUCTORS AND THE NEUTRAL. |
| | |
| | 5)NOTE: PLEASE SEE FS 553.80(2)(B) WITH |
| | RESPECT TO DESIGN PROFESSIONAL AND |
| | REPEAT COMMENTS. |
| | |
| | 6)NOTE: PLEASE SEE THE RECORDED NOC |
| | SUBMITTED ON 12/19/05 HAS SINCE EXPIRED |
| | PER FS 713.13(2). PLEASE KNOW, IF WORK H |
| | HAS NOT COMMENCED WITHIN 90 DAYS OF |
| | RECORDING SAID NOC, THEN THE NOC WILL |
| | BECOME VOID. |
| | THIS WILL NEED TO BE RE-RECORDED BEFORE |
| | PICKING UP PERMIT. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW AND IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |