| 2005-08-17 00:00:00 | DENIED |
| | 1)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT (2) COPIES OF A SIGNED AND |
| | SEALED SURVEY. |
| | |
| | 4) THE CITY AMENDMENTS TO FBC 1804.1.7 |
| | REQUIRE THE FINISH FLOOR ELEVATION OF A |
| | MONOLITHIC FOUNDATION TO BE A MINIMUM OF |
| | 4" ABOVE GRADE AT HABITABLE AREAS. FBC |
| | 18O4.1.3 REQUIRES THE BOTTOM OF FOOTINGS |
| | TO BE A MINIMUM OF 4" BELOW GRADE. |
| | SPECIFY THIS ON THE SECTIONS ON SHEETS 2 |
| | AND 11. |
| | |
| | 5) THE INTERNAL PRESSURE COEFFICENT ON |
| | SHEET 3 DOES NOT HAVE THE PLUS AND MINUS |
| | SIGNS. SEE ASCE 7-98. |
| | |
| | 6) PROVIDE FIREPLACE AND CHIMNEY |
| | SECTIONS AND DETAILS. SEE FBC 2114 AND |
| | 2804. |
| | |
| | 7) PROVIDE A STAIR DETAIL. SPECIFY THE |
| | TREAD WIDTH, RISER HEIGHT, ETC. SEE FBC |
| | 1007.3. |
| | |
| | 8) PROVIDE STAIR AND BALCONY GUARDRAIL |
| | DETAILS. SEE FBC 1015, 1026.5 AND |
| | 1608.2. |
| | |
| | 9) PROVIDE HANDRAIL DETAILS. SEE FBC |
| | 1007.5. |
| | |
| | 10) SPECIFY THE SQUARE FOOT BREAKDOWN OF |
| | THE STRUCTURE. |
| | |
| | 11) SPECIFY THE SIZE AND LOCATIONS OF |
| | THE ATTIC ACCESSES PER FBC 2309.6. |
| | |
| | 12) SPECIFY ATTIC VENTILATION PER FBC |
| | 2309.7. |
| | |
| | 13) THERE IS NO CHIMNEY SHOWN ON THE |
| | ELEVATIONS FOR THE MASONRY FIREPLACE. |
| | |
| | 14) THE DESIGN PRESSURES FOR COMPONENTS |
| | AND CLADDING GIVEN ON SHEET 7 ARE FOR |
| | EXPOSURE CATEGORY B. THE EXPOSURE |
| | CATEGORY YOU INDICATED FOR YOUR DESIGN |
| | ON SHEET 3 IS C. PLEASE ADJUST VALUES |
| | USING FBC TABLE 1606.2D OR CHANGE |
| | CATEGORY TO B. |
| | |
| | 15) THE GARAGE DOOR PRESSURES ARE ALSO |
| | FOR EXPOSURE B. THE CORRECT TABLE IS FBC |
| | 1606.2E. |
| | |
| | 16)SOME OF THE DIMENSIONS ARE MISSING |
| | FROM THE SECOND FLOOR PLAN. |
| | |
| | 17) SPECIFY THE LOCATIONS AND MATERIAL |
| | FOR THE DRAFTSTOPPING AT THE |
| | FLOOR/CEILING ASSEMBLY AS REQUIRED BY |
| | FBC 2305.2.2. |
| | |
| | 18) PROVIDE A DETAIL OF THE BEAM |
| | SUPPORTING THE SECOND FLOOR EXTERIOR |
| | MASONRY WALL AT THE MASTER BATH. |
| | |
| | 19) PROVIDE A BEAM/LINTEL SCHEDULE ON |
| | THE PLANS. |
| | |
| | 20) PROVIDE A CONNECTOR SCHEDULE FOR THE |
| | ROOF TRUSSES. |
| | |
| | 21) PROVIDE FASTENING DETAILS FOR THE |
| | SISTERED OUTLOOKERS AT THE ROOF |
| | OVERHANG. |
| | |
| | 22) REVISE THE ROOF SHEATHING FASTENING |
| | NOTES. THE CITY AMENDMENTS TO FBC TABLE |
| | 2306.1 REQUIRES 8D RING-SHANK NAILS AT |
| | 4"OC AT EDGES AND 6"OC INTERMEDIATE IN |
| | ZONE 3. ZONE 3 INCLUDES THE OUTSIDE |
| | CORNERS OF HIP ROOFS. |
| | |
| | 23) SPECIFY THE LOCATION OF THE VERTICAL |
| | REINFORCEMENT AT THE SECOND FLOOR |
| | MASONRY WALLS. |
| | |
| | 24) PROVIDE BUCK DETAILS FOR THE |
| | EXTERIOR SWING DOORS AND GARAGE DOORS. |
| | |
| | 25) PRODUCT APPROVALS SUBMITTED |
| | WITH PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE |
| | AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| | WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| | BE SUBMITTED WITH A COVER SHEET THAT |
| | LISTS THE PRODUCT IDENTITY NUMBER FROM |
| | THE STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |
| | SUBMIT STATE OR LOCAL PRODUCT APPROVALS |
| | FOR THE EXTERIOR WINDOWS, DOORS, GARAGE |
| | DOORS, ROOFING MATERIAL, TRUSS |
| | CONNECTORS, ETC. (THE NOAS THAT WERE |
| | SUBMITTED ARE EXPIRED.) |
| | |
| | 26) THE PLANS SPECIFY THE WINDOWS AS |
| | IMPACT RESISTANT. HOWEVER, THE PRODUCT |
| | APPROVALS SUBMITTED ARE FOR NON-IMPACT |
| | RATED WINDOWS. STORM PANELS WILL BE |
| | REQUIRED FOR NON-IMPACT GLAZING. |
| | |
| | 27) SUBMIT STATE PRODUCT APPROVALS, KEY |
| | PLANS AND INSTALLATION SCHEDULES (2 |
| | SETS) FOR THE STORM PANELS. SPECIFY THE |
| | TYPE OF MOUNT, TYPE OF FASTENER AND |
| | FASTENER SPACING FOR EACH OPENING. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |
| | |
| | |
| | |
| | |