| Plan Review Notes For Permit 05071195 |
| Permit Number |
05071195 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-06 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)SHOW THE MEANS OF ESCAPE | | | FBC1005.4.5.NOTE WHICH ROOM THIS IS | | | LOCATED IN; CANNOT BE THROUGH A LOCKABLE | | | DOOR OR THROUGH THE GARAGE. | | | | | | 2.)FLORIDA STATE OR LOCAL PRODUCT | | | APPROVAL REQUIRED, FAC9B72.A LETTER | | | INDICATING THAT THIS PRODUCT HAS STATE | | | APPROVAL WAS SUBMITTED; HOWEVER TO SHOW | | | COMPLIANCE YOU ARE TO PRINT THE ACTUAL | | | STATE APPROVAL IF ONE IS AVAILABLE.IF | | | THIS IS NOT AVAILABLE, APPLY FOR A LOCAL | | | PRODUCT APPROVAL.THE LETTER SUBMITTED | | | FROM THE MANUFACTURER STATING THAT | | | APPROVAL IS AVAILABLE AND THAT THE | | | BUILDING DEPARTMENT DOES NOT UNDERSTAND | | | THE RULE IS NOT SHOWING CODE COMPLIANCE | | | WITH FAC9B72. |
|