| 2005-09-20 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.) THE TEST REPORT SUBMITTED TO SHOW |
| | CODE COMPLIANCE FOR THE BUTT GLASS BAY |
| | WINDOW WAS AN EXPERIMENTAL REPORT WHICH |
| | DOES NOT APPEAR TO BE IN CONFORMANCE |
| | WITH THE TESTING STANDARDS REQUIRED BY |
| | FBC1707.4.2.1. |
| | |
| | 2.)THE TEST REPORT SUBMITTED DOES NOT |
| | PROVIDE ENOUGH INFORMATION ABOUT THE |
| | WINDOW UNIT TESTED.FROM THE TEST |
| | REPORT I CANNOT DETERMINE IF IT IS THE |
| | PRODUCT YOU ARE PROPOSING TO INSTALL, |
| | ARCH ALUMINUM SERIES 4500, OR IF AN |
| | EQUIVALENT PRODUCT WAS TESTED. |
| | |
| | 3.)THE WINDOW SIZES PROPOSED IS LARGER |
| | IN BOTH OVERALL SIZE AS WELL AS THE |
| | FRONT PANEL SIZE.IT IS NOT CLEAR HOW |
| | YOU HAVE ARRIVED AT THE DESIGN PRESSURE. |
| | |
| | 4.)THE ENGINEERING FOR THE 84X144 |
| | OPENING DOES NOT INDICATE WHICH ARCH |
| | ALUMINUM PRODUCT YOU ARE USING. |
| | |
| | 5.)ORIGINAL SIGNATURE REQUIRED ON THE |
| | LOCAL PRODUCT APPROVAL APPLICATION. |
| | |
| | 6.)WHEN RESUBMITTING, ALL DOCUMENTS |
| | WHICH YOU ARE USING TO SHOW CODE |
| | COMPLIANCE (SUCH AS ENGINEERING, |
| | CALCULATIONS OR TEST REPORTS) ARE TO BE |
| | SIGNED, SEALED ORIGINALS.ONCE A LOCAL |
| | PRODUCT APPROVAL IS ISSUED, THE ORIGINAL |
| | CAN REMAIN ON FILE AND COPIES CAN BE |
| | SUBMITTED FOR INDIVIDUAL PERMITS. |