2005-09-20 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) THE TEST REPORT SUBMITTED TO SHOW
 CODE COMPLIANCE FOR THE BUTT GLASS BAY
 WINDOW WAS AN EXPERIMENTAL REPORT WHICH
 DOES NOT APPEAR TO BE IN CONFORMANCE
 WITH THE TESTING STANDARDS REQUIRED BY
 FBC1707.4.2.1.
  
 2.)THE TEST REPORT SUBMITTED DOES NOT
 PROVIDE ENOUGH INFORMATION ABOUT THE
 WINDOW UNIT TESTED.FROM THE TEST
 REPORT I CANNOT DETERMINE IF IT IS THE
 PRODUCT YOU ARE PROPOSING TO INSTALL,
 ARCH ALUMINUM SERIES 4500, OR IF AN
 EQUIVALENT PRODUCT WAS TESTED.
  
 3.)THE WINDOW SIZES PROPOSED IS LARGER
 IN BOTH OVERALL SIZE AS WELL AS THE
 FRONT PANEL SIZE.IT IS NOT CLEAR HOW
 YOU HAVE ARRIVED AT THE DESIGN PRESSURE.
  
 4.)THE ENGINEERING FOR THE 84X144
 OPENING DOES NOT INDICATE WHICH ARCH
 ALUMINUM PRODUCT YOU ARE USING.
  
 5.)ORIGINAL SIGNATURE REQUIRED ON THE
 LOCAL PRODUCT APPROVAL APPLICATION.
  
 6.)WHEN RESUBMITTING, ALL DOCUMENTS
 WHICH YOU ARE USING TO SHOW CODE
 COMPLIANCE (SUCH AS ENGINEERING,
 CALCULATIONS OR TEST REPORTS) ARE TO BE
 SIGNED, SEALED ORIGINALS.ONCE A LOCAL
 PRODUCT APPROVAL IS ISSUED, THE ORIGINAL
 CAN REMAIN ON FILE AND COPIES CAN BE
 SUBMITTED FOR INDIVIDUAL PERMITS.