| 2005-07-27 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.) FROM PERMIT NUMBER 05030986: |
| | |
| | THE SAME ENGINEERING THAT WAS DENIED |
| | PREVIOUSLY WAS RESUBMITTED.THE |
| | PRESSURES ON THE PLAN FOR THESE OPENINGS |
| | ARE +31/-41, SHEET A2.THE ENGINEERING |
| | (FOR THE BUTT GLASS) HAS A DP OF |
| | +30.1/-32.8.PLEASE ADDRESS BEFORE |
| | APPLYING FOR A PERMIT - DO NOT SUBMIT |
| | THE SAME PAPERWORK UNLESS YOU REVISE |
| | SHEET A2 AS DISCUSSED WITH THE ENGINEER. |
| | |
| | THERE WAS A WINDOW SCHEDULE FROM THE |
| | ENGINEER DATED 6/14/05.IT DOES NOT |
| | HAVE ALL OF THE BUTT GLASS OPENINGS |
| | (THERE SHOULD BE 3) AND ALSO DOES NOT |
| | HAVE DESIGN PRESSURES.ALSO TO AVOID |
| | CONFUSION PLEASE HAVE THE ARCHITECT |
| | REVISE A2 IF HE WISHES TO CHANGE THE |
| | DESIGN PRESSURES FOR THESE OPENINGS. |
| | OTHERWISE SUBMIT COMPLIANT PAPERWORK |
| | MEETING THE DESIGN PRESSURES ON THE |
| | PLAN. |
| | |
| | 2.)THERE IS ALSO ENGINEERING IN THE |
| | PACKAGE WHICH WAS DENIED WHICH HAS |
| | NOTHING TO DO WITH THIS GLASS |
| | APPLICATION.PLEASE RETAIN THAT |
| | PAPERWORK. |
| | |