Plan Review Notes
Plan Review Notes For Permit 05071160
Permit Number 05071160
Review Stop E
Sequence Number 4
Notes
Date Text
2006-02-06 00:00:00********* UNSAT **************
  
 ** PLEASE SEE SOME ITEMS FROMPLANS
 REDLINED ON PREVIOUS REVIEW NEED TO BE
 ADDRESSED.
  
  
 1)NOTE: PANEL H SHOWS #8'S FOR FEEDERS
 TO EXISITNG PANEL "P" AND RISER SHOWS
 #6'S.
 PLEASE ADJUST, 310.16,240.4
  
 2)NOTE: PLEASE SEE MININUM VA FOR
 WASHER/LAUNDRY CIRCUIT SHALL BE 1500VA,
 220.16,210.11.
  
 3)NOTE: PLEASE CORRELATE RISER AND PANEL
 SCHEDULES. PLEASE SEE RISER SHOWS THE CU
 BEING FED FROM PANEL "H", HOWEVER PANEL
 "H" DOES NOT LIST THIS CU NOR DOES IT
 LIST THE AHU.
 PLEASE HOWEVER SEE A PANEL SCHEDULE
 SUBMITTED FOR PANEL "S" WHICH INDICATES
 BOTH THE CU AND AHU BEING FED FROM THIS
 INDOOR PANEL.
 PLEASE CORRECT AND REVISE PLANS AS
 NEEDED.215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]