| Plan Review Notes For Permit 05071160 |
| Permit Number |
05071160 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2006-02-06 00:00:00 | ********* UNSAT ************** | | | | | | ** PLEASE SEE SOME ITEMS FROMPLANS | | | REDLINED ON PREVIOUS REVIEW NEED TO BE | | | ADDRESSED. | | | | | | | | | 1)NOTE: PANEL H SHOWS #8'S FOR FEEDERS | | | TO EXISITNG PANEL "P" AND RISER SHOWS | | | #6'S. | | | PLEASE ADJUST, 310.16,240.4 | | | | | | 2)NOTE: PLEASE SEE MININUM VA FOR | | | WASHER/LAUNDRY CIRCUIT SHALL BE 1500VA, | | | 220.16,210.11. | | | | | | 3)NOTE: PLEASE CORRELATE RISER AND PANEL | | | SCHEDULES. PLEASE SEE RISER SHOWS THE CU | | | BEING FED FROM PANEL "H", HOWEVER PANEL | | | "H" DOES NOT LIST THIS CU NOR DOES IT | | | LIST THE AHU. | | | PLEASE HOWEVER SEE A PANEL SCHEDULE | | | SUBMITTED FOR PANEL "S" WHICH INDICATES | | | BOTH THE CU AND AHU BEING FED FROM THIS | | | INDOOR PANEL. | | | PLEASE CORRECT AND REVISE PLANS AS | | | NEEDED.215.5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|