| 2005-08-16 00:00:00 | ********* UNSAT ********** |
| | |
| | |
| | 1) NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | PLEASE SEE BATH GFI IS ALSO SHOWN ON |
| | WITH OUTSIDE RECEPT. |
| | PLEASE SEE BATH SHALL NOT HAVE ANY OTHER |
| | RECEPTS. |
| | MUST BE 20A AND #12 |
| | |
| | 2)NOTE: PLEASE SHOW OUTLET SPACING PER |
| | 210.52. 2',6`,12` RULE. |
| | PLEASE SOME MISSING. |
| | |
| | 3)NOTE: PLEASE SEE MISSING GFI RECEPTS |
| | PER 210.52C1 ALONG KITCHEN COUNTERSPACE. |
| | 210.8A6 |
| | |
| | 4)NOTE: PLEASE SEE MISSING FRONT AND |
| | REAR GFI RECEPTS PER 210.52E |
| | |
| | 5)NOTE: PLEASE SEE MISSING GFI FOR A/C |
| | CU. 210.63, 210.8 |
| | |
| | 6)NOTE: PLEASE SEE MISSING A/C CU NOT |
| | SHOWN ON PLANS ALONG WITH DISCONNECT NOT |
| | SHOWN FOR CU.? 440.11 |
| | |
| | 7)NOTE: PLEASE SEE PANEL SCHEDULE |
| | INDICATES 50A OCP FOR HEAT/ AHU, |
| | HOWEVER, PLEASE SEE MECH PLANS WHICH |
| | SHOWS A 10KW HEATSTRIP. PLEASE SEE |
| | 424.3B FOR A MIN OF 125% FOR OCP AND SEE |
| | 310.16 FOR MIN AWG. |
| | |
| | 8)NOTE: PLEASE SEE 410.8 FOR MIN |
| | CLEARENCE IN CLOSETS FOR LIGHTING |
| | FIXTURES AND TYPES OF FIXTURES. |
| | |
| | 9)NOTE: PLEASE SEE PLANS INDICATE PANELS |
| | C&H, HOWEVER PANEL SCHEDULES SUBMITTED |
| | SHOW PANELS H&P? PLEASE CORRELATE. |
| | PLEASE SHOW PANEL LOCATIONS ON PLANS |
| | ALONG WITH SERVICE LOCATION. PLEASE |
| | INDICATE IF PANELS/ SERVICE IS NEW OR |
| | EXISTING? |
| | PANELS ARE SHOWN AS NEW. |
| | PLEASE SEE PANEL "P" IS SHOWN AS BLANK, |
| | WITH NO INFORMATION ON PANEL, CIRCUITS, |
| | SIZE ETC . |
| | PLEASE SEE PANEL "H" SHOWS A 1-POLE |
| | CIRCUIT TO FEED PANEL "P".? |
| | PLEASE SEE PANEL "H" IS SHOWN AS A MLO |
| | WITH NO MAIN. PLEASE CLARIFY WHERE MAIN |
| | IS ? |
| | 215.5,240.24,230.70,310.16,240.24 ETC |
| | IF THESE ARE ALL NEW, PLEASE SEE THE |
| | FOLLOWING COMMENT. |
| | |
| | 10)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 11)NOTE: PLEASE SEE 2002 NEC 210.12, |
| | WHICH REQUIRES ARC FAULT PROTECTION FOR |
| | "ALL OUTLETS' IN BEDRMS. PLEASE SEE THIS |
| | INCLUDES,,, LTS, FANS, SD'S, RECEPTS |
| | ETC. |
| | PLEASE SEE ONLY TWO CIRCUITS SHOWN ON |
| | PANEL SCHEDULE SHOW ARC FAULT |
| | PROTECTION. |
| | |
| | 12)NOTE: PLEASE SHOW ALL ROOM AREA/ |
| | DESIGNATIONS ON PLANS. |
| | |
| | 13)NOTE: PLEASE CALRIFY 40A OCP FOR |
| | DRYER, THIS IS ONLY A NOTE: |
| | |
| | 14)NOTE: PLEASE INCLUDE LOAD |
| | CALCUALTIONS FOR NEW OR EXISTING |
| | SERVICE. |
| | |
| | 15)NOTE: PLEASE SEE BLDG REVIEW COMMENTS |
| | FOR VALUATION ADJUSTMENT FOR SCOPE OF |
| | WORK PROPOSED. THIS IS REQUIRED TO BE |
| | BASED ON FAIR MARKET VALUE, EVEN WHEN |
| | DONE BY AN OWNER BUILDER. PLEASE SEE FBC |
| | 104.6.5, CITY OF WEST PALM BEACH |
| | ADMINISTRATIVE CODE. |
| | THIS IS TO INCLUDE ALL LABOR AND |
| | MATERIALS , EVEN IF MATERIALS ARE OWNER |
| | SUPPLIED. |
| | |
| | 16)NOTE: PLEASE SEE PLANS DO NOT |
| | INDICATE ANY NEW "PHONE " LOCATIONS. |
| | THIS IS NOT REQUIRED AND IS ONLY A NOTE. |
| | IF PHONE LOCATIONS/WIRING WILL BE |
| | INSTALLED UNDER THIS PERMIT, PLEASE SHOW |
| | LOCATIONS ON THIS PLANS. |
| | IF PHONE WIRING IS NOT SHOWN, A SEPARATE |
| | LAYOUT AND PERMIT APPLICATION WILL BE |
| | REQUIRED AT A LATER DATE. THIS IS ONLY A |
| | NOTE AND NO CORRECTIONS ARE NEEDED. |
| | THIS WOULD ALSO BE RELATED TO ANY OTHER |
| | POSSIBLE LOW VOLTAGE INSTALLATIONS WITH |
| | THE EXCEPTION TO ALARM SYSTEMS. |
| | ALARMS ARE SEPARATE PERMITS. |
| | |
| | 17)NOTE: IF CARRIAGE LTS ARE INSTALLED |
| | UNDER THIS PERMI ALSO, A DISCONNECTING |
| | MEANS AT DETACHED BLDG WILL BE REQUIRED |
| | 225.31 |
| | |
| | PLEASE SEE THERE ARE MANY ITEMS REDLINED |
| | ON PLANS FOR SOME OF THE ABOVE COMMENTS. |
| | PLEASE SEE NOT ALL LOCATIONS ARE NOTED |
| | DUE TO MISSING INFORMATION. |
| | PLEASE BE SURE TO SEE ANY COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | ANDONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE SEE THAT ONE COPY OF ANY |
| | OLD/VOIDED SHEETS REMOVED SHALL BE |
| | SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |