2005-08-05 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 THE CERTIFICATE OF AUTHORIZATION NUMBER
 ISSUED BY THE STATE IS SUPPOSED TO BE
 LISTED ON THE TITLE BLOCK, NOT THE
 STATUTE OR CODE REFERENCE.
  
 SEE 8-1.4.2 NFPA-72 FOR PLACEMENT OF
 SMOKE DETECTORS IN PROXIMITY TO THE
 KITCHEN.
  
 INDICATE IF THE SERVICE IS NEW OR
 EXISTING. PROVIDE THE AIC RATING PER
 110.9 & 10.
  
 SEE 250.50 AND 250.66 FOR GROUNDING
 REQUIREMENTS. THE #6 TO FOOTER STEEL
 DOWN SIZED FROM #4 IS NOT COMPLIANT.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW