| 2005-08-05 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | THE CERTIFICATE OF AUTHORIZATION NUMBER | | | ISSUED BY THE STATE IS SUPPOSED TO BE | | | LISTED ON THE TITLE BLOCK, NOT THE | | | STATUTE OR CODE REFERENCE. | | | | | | SEE 8-1.4.2 NFPA-72 FOR PLACEMENT OF | | | SMOKE DETECTORS IN PROXIMITY TO THE | | | KITCHEN. | | | | | | INDICATE IF THE SERVICE IS NEW OR | | | EXISTING. PROVIDE THE AIC RATING PER | | | 110.9 & 10. | | | | | | SEE 250.50 AND 250.66 FOR GROUNDING | | | REQUIREMENTS. THE #6 TO FOOTER STEEL | | | DOWN SIZED FROM #4 IS NOT COMPLIANT. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|